Counter 1-6 - Siemens SIMOCODE 3UF Programming And Operating Manual

Table of Contents

Advertisement

In total, 6 counters (1 to 6) for the SIMOCODE pro V PN basic unit are available.
Note
The time between the events to be counted depends on:
• the input delay
• the device cycle time.
Note
The actual value remains the same:
• during parameterization or failure of the supply voltage
• if there are simultaneous input signals at Input + and Input -.
Note
The output is always 0 if a reset is pending.
13.2.2

Counter 1-6

Counter 1-6
Limit
Input +
Input -
Reset
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
The maximum value that can be reached when counting and where
the counter issues an output signal.
Range: 0 - 65535
Increases the actual value by 1.
Activation by any signal (any sockets e.g. device inputs, control bits
from PROFINET, etc.
Decreases the actual value by 1.
Activation by any signal (any sockets e.g. device inputs, control bits
from PROFINET, etc.
Resets the Counter to 0 (count value and output).
Activation by any signal (any sockets e.g. device inputs, control bits
from PROFINET, etc.)
Logic Modules
13.2 Counter
119