17.10
Faults
Faults
Different warnings are indicated via checkboxes in the "Faults" register of the target system
> Faults/Warnings/Events mask.
Controlling
Indication
Execution ON command
Execution stop command
Feedback (F) ON
Feedback (F) OFF
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Meaning/Possible cause/Acknowledgement/Error processing
The motor feeder could not be turned on after an ON command.
Possible causes:
Main circuit is interrupted (fuse, circuit breaker)
•
Motor contactor or contactor control is defective
•
Parameter execution time is too short.
•
Acknowledge with "Reset" or OFF command/counter command.
The motor feeder could not be turned off after a Stop command.
Possible causes:
The contactor contact is welded
•
Parameter execution time is too short
•
The "Open" end position has not been reached during the
•
parameterized runtime (only in the case of the "Slider" and
"Valve" control functions.
Following fault rectification, acknowledge with "Reset".
The motor feeder could not be turned on after an ON command.
Possible causes:
Main circuit is interrupted (fuse, circuit breaker)
•
Motor contactor or contactor control is defective, "Execution
•
time" parameter is too short.
Only in the case of the "Slider/Solenoid valve" control
•
function. The end position "CLOSE" has not been reached
during the parameterized runtime.
Following fault rectification, acknowledge with "Reset" or OFF
command.
The current flow in the motor feeder was interrupted without the
motor feeder being turned off.
Possible causes:
Main circuit is interrupted (fuse, circuit breaker, main switch)
•
Motor contactor or contactor control is defective.
•
Acknowledge with "Reset" respectively OFF command.
Online Settings and Displays
17.10 Faults
153