External Faults 1-6 - Siemens SIMOCODE 3UF Programming And Operating Manual

Table of Contents

Advertisement

Reset
Response
Reset also by
12.3.2

External Faults 1-6

12.3.2.1
External Faults 1-6
External Faults 1-6
The External Fault 1function block can be used to monitor any statuses and/or external
devices, to generate fault messages and, if necessary, to switch off the motor. To do this, the
Inputs (plugs) of the External Fault function blocks must be connected to any sockets (e.g.
device inputs, control bits from PROFINET, etc.). External faults can also be "marked" in
SIMOCODE pro. This facilitates their allocation to the actual malfunction.
Example: Monitoring the rotational speed of the motor using an external rotational-speed
monitor.
The External Fault function block consists of:
● 2 plugs (1 plug for setting, 1 plug for resetting)
● 1 "Event - External Fault" socket. This is set when a signal is pending at the Input.
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Acknowledgment the "External Fault" using any signal (any socket , e.g.
device inputs, control bits from PROFINET, etc.)
Specification of the response to an External Fault when activated via
the Input (see table response)
Specification of further (common) acknowledgement options using
additional reset types:
• TEST/RESET buttons on the Basic Unit and the Operator Panel
(panel reset)
• Remote reset: Acknowledgement via Reset 1-3, control bit "Reset"
command
• Auto reset: The trip resets itself after the cause has been eliminated
(after removal of the activation signal)
• OFF command reset: "OFF" control command resets the fault.
Standard Functions
12.3 External Fault
91