Monitoring Functions
9.2 Current Limits
9.2.2
I> (upper limit)
Trip level (CiR), warning level (CiR)
When monitoring Current Limits I> (upper limit), 2 different response levels, I> (upper limit)
trip level and I> (upper limit) warning level, can be parameterized and monitored. If the
current of one or more phases exceeds the response level, Current Limits monitoring is
activated.
Trip level
Warning level
Response, Delay (CiR) at trip level
Here you can set:
● how SIMOCODE pro should respond when the trip level is overshot
● the delay time.
Response
Disabled
Signaling
Warning
Tripping
Delay
Preset
Response, Delay (CiR) at warning level
Here you can set:
● how SIMOCODE pro should respond when the warning level is overshot
● the delay time.
Response
Disabled
Signaling
Warning
Tripping
Delay
Preset
50
0 to 1020 % of I
in 4 % increments
s
0 to 1020 % of I
in 4 % increments
s
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Trip level
X
X
-
X
0 to 25.5 s
0.5 s
Warning level
X
X
X
-
0 to 25.5 s
0.5 s
SIMOCODE PRO V PN FDI