Password Input; Monitoring And Analysis Parameters; Cp.01 Inverter State - KEB COMBIVERT R6 Instruction Manual

Power supply and regenerative unit
Hide thumbs Also See for COMBIVERT R6:
Table of Contents

Advertisement

5.4

Password input

No.
Name
CP.00
password input
Ex works the COMBIVERT R6-N is supplied without password protection, i.e. all changea-
ble parameters can be adjusted. After parameterizing the inverter can be secured against
unauthorized access (locking: 100 and release: 200). The adjusted mode is stored.
5.5

Monitoring and analysis parameters

The following parameters serve for the functional monitoring during operation.
No.
Name
CP.01
inverter state
The status display shows the actual working condition of the COMBIVERT.
Status messages
rEGEn
Regeneration active (regenerative operation)
bbL
Count down of the base-block time, R6-N released
noP
„no Operation" control release not bridged, modulation switched off
Mains power failure; regenerative operation is further possible, if the disconnect-
nEtoF
ing time E.nEt (Pn.14) > 0 s
rinit
Re-initialisation
Stb
R6-N regenerative unit in stand-by operation (motor operation)
Error Messages
E.EF
External Fault, error message by an external unit
„Error! Mains frequency", the mains frequency deviates more than 5 %. The max.
E.FnEt
mains frequency deviation can be adjusted in the application mode with CS.03.
Error "Fault reset level reached" is triggered when the adjusted value in parameter
E.Frlr
Pn.15 is reached within one hour. The error can be reset.
Error! Charging circuit, load-shunt defective or wrong or input voltage too low. This
E.LSF
message is displayed for a short time during the power-on phase (no error mes-
sage follows).
E.nEt
„Error! net, one or more phases are missing
E.nOH
No overheat, over-temperature error not present (E.OH), error can be reset.
E.nOL
No overload, cooling time after E.OL is up , error can be reset.
E.OC
„Error! Overcurrent", output current too high or ground fault
E.OH
„Error! Overtemperature", overheating at heat sink (see „Technical data")
E.OHI
„Error! Interior temperature", temperature in the interior > 95 °C
E.OL
„Error! Overload", overload monitoring of the regenerative unit has responded
E.OP
„Error! Overvoltage", DC link voltage too high
E.Pu
„Error in power unit", power unit code is missing, load shunt relay defective
Password input
r/w
Enter based on
r/w
Enter based on
continued on the next page
Ud.01
ru.00
43