Monitoring And Analysis Parameters - KEB COMBIVERT R6-S Series Instruction Manual

Power supply and regenerative unit
Hide thumbs Also See for COMBIVERT R6-S Series:
Table of Contents

Advertisement

Approach of the working meters
The displayed values of the working meters offer only an estimate value because
of measurement and calculation inaccuracies. These displayed values are un-
suitable for tariff applications and cannot replace any measuring devices.
5.4

Monitoring and analysis parameters

The following parameters serve for the functional monitoring during operation.
No.
Name
CP.01
status display
The status display shows the actual working conditions of the COMBIVERT.
Status Messages
rEGEn
Regeneration active (regenerative operation)
bbL
Count down of the base-block time, R6-S released
noP
„no Operation" control release not bridged, modulation switched off
Mains power failure; regenerative operation is further possible, if the disconnect-
nEtoF
ing time E.nEt (Pn.14) > 0 s
Stb
R6-S regenerative unit in stand-by operation (motoric operation)
Error Messages
„ERROR ! overheat choke", temperature monitoring of the commutation choke has
E.dOH
triggered and the cooling-off period is up.
E. EF
„ERROR ! external fault", error message by an external unit
„ERROR ! mains frequency", the mains frequency deviates more than 5 %. The
E.FnEt
max. mains frequency deviation can be adjusted in the application mode with
CS.03.
ERROR! load-shunt defective or input voltage too low. This message is displayed
E.LSF
for a short time during the power-on phase (no error message follows).
E.nEt
„ERROR net", one or more phases are missing
E.nOH
no ERROR overheat pow.mod. (E.OH) not any longer present, error can be reset.
E.nOL
No Over Load, cooling time after E.OL is up , error can be reset.
E. OC
„ERROR overcurrent, output current too high or ground fault
E. OH
„ERROR overheat pow.mod.", overheating at heat sink (see „Technical data")
E.OHI
„ERROR overheat internal", temperature in the interior > 70°C
E. OL
„ERROR overload, overload monitoring of the regenerative unit has responded
E. OP
„ERROR overpotential, DC link voltage too high
E.PFd
„ERROR initialisation", power failure (phase) during the initialisation phase
E. Pu
„ERROR power unit", power unit code is missing, load shunt relay defective
E.Puci
„ERROR pow.unit code inv." power unit code is invalid
E.Puch „ERROR power unit changed".
E.PUIN „ERROR net", ripple of the rectified mains voltage too high
US - 38
r/w
Enter
Origin
ru.00
continued on the next page