Connection Of The Control Board Version S; Assignment Of The Control Terminal Strip X2A; Assignment Of Socket X2B - KEB Combivert R6 Instruction Manual

Power supply and regenerative unit
Hide thumbs Also See for Combivert R6:
Table of Contents

Advertisement

Connection of the Control Board
4.5

Connection of the control board version S

4.5.1 Assignment of the control terminal strip X2A

PIN Function
10
24V input
11
Mass
12
Digital input 1
13
Digital input 2
14
Digital input 3
15
Digital input 4
16
Digital in-/output
17
24 V-output
18
Mass
19
Digital output 1
20
Digital output 2
21
Analog output
22
24 V-output
23
Mass
24
Relay 1 / NO contact
25
Relay 1 / NC contact
26
Relay 1 / switching
contact
27
Relay 2 / NO contact
28
Relay 2 / NC contact
29
Relay 2 / switching
contact
*)
The relay outputs must be operated with max. 48 V DC protective separation voltage to guarantee the CE standard. After consultation KEB
a current of max. 1 A DC is permissible for 120 V AC.

4.5.2 Assignment of socket X2B

RJ45 socket for phase synchronization and tem-
perature sensor
1
The connection is made with a standard patch cable 1:1 with the socket X2B, X2C or X2D at the commutation
reactor.
10 11 12 13 14 15 16 17 18 19 20 21 22 23
Core cross-section 0,14...1,5 mm², tightening torque 0,5 Nm
Name
Description
Uin
External supply of the control board
COM
Reference potential
ST
Control release / reset
I1
programmable
I2
programmable
I3
programmable
I/O (I4)
Active signal (connection of all R6
at parallel operation in master-slave
procedure)
Uout
Voltage supply for in- and outputs
COM
Reference potential
O1
Transistor output (DC > CP.19)
O2
Transistor output (error message)
ANOUT
Difference to mains frequency (CP.18)
Uout
see terminal 17
COM
Reference potential
RLA
Relay output
RLB
Ready signal (no error)
RLC
FLA
Relay output
FLB
(DC > CP.19 and tightened load-shunt)
FLC
8
X2A
24 25 26 27 28 29
No.
Name
Function
1
t1
Connection for temperature sensor (option)
2
t2
3
U13_syn Synchronization phase 1 / 3
4
reserved
5
U21_syn Synchronization phase 2 / 1
6
reserved
7
U32_syn Synchronization phase 3 / 2
8
reserved
Specifications
23...30 V DC / 1 A
Ri: 4,4 kΩ
ca. 24 V / max. 100 mA
I
: 25 mA
max
I
: 25 mA
max
0...±10 V / max. 5 mA
max. 30 V DC *)
0,01...2 A DC
max. 30 V DC *)
0,01...2 A DC
GB - 31