52 - Program Zones (cont'd)
01 Final
Zones programmed as Final initiate the unsetting procedure and terminate setting procedure; opening the
Final zone when the system or group is set starts the entry timer; opening and then closing the Final zone
during the exit procedure sets the system or assigned groups, providing all the zones are closed. The opening
(+) and closing (–) of Final zones during the setting and unsetting procedures are recorded in the event log.
Pressing the
key when programming a Final zone doubles the entry time of the group.
Opening a Final zone during the exit time is not reported on the keypad as an open zone; the Entry/Exit
Horns bleep rapidly to indicate that the zone is open.
NOTE: The termination feature of a Final zone can be extended to terminate the setting of multiple groups
by pressing the
02 Exit
Zones that protect the entry and exit routes are programmed as Exit. During the setting and unsetting proce-
dures Exit zones have a non-alarm operation. If the Exit zone is activated while the system is set - without the
unsetting of the group being initiated - an Intruder alarm condition is activated.
Opening an Exit zone during the exit time is not reported on the keypad as an open zone; the Entry/Exit
Horns bleep rapidly to indicate that the zone is open.
NOTE: The Exit zone can be assigned to multiple groups by pressing the
the zone. This allows an Exit zone to be activated in a group which is not currently being unset
without activating an Intruder alarm. Refer to the Star
03 Intruder
The Intruder function is inactive when the system is unset. When the system is set, activation of an Intruder
zone causes a full alarm activation that requires to be reset with a code authorized for System Reset - refer
to option 51.6 = PARAMETERS.System Reset and option
51.55.3 = PARAMETERS.Confirm.Reduce Reset.
All zones are programmed as Intruder by default; this includes the zones on RIOs that are added to the
system at a later date.
04 24 Hours
The 24 Hours zone function is continuously operational. In the unset state, activation of the zone function
generates a local alarm condition (the Intruder outputs are not activated). If the zone is activated while the
system is set, the 24 Hours function operates the same as an Intruder function and results in a full alarm
condition. The 24 Hours zone function requires a system reset following an activation in both the set and unset
conditions.
05 Security
The operation of the Security zone function is identical to the 24 Hours zone function, except a Security
zone activation in the unset generates a local alarm (Horn outputs activated) that does not require a system
reset; any valid code (type 2 or above) cancels the alarm and resets the system. An activation in the set state
generates a full alarm that requires a system reset. The activation (+) and restoration (–) of Security zones is
recorded in the event log.
key when assigning a group to the zone. Refer to the Star
Galaxy 3 Series Programming Manual
Group Function.
76
Group Function.
key when assigning a group to