Galaxy 3 Series Programming Manual
51 - Parameters (cont'd)
35 = Fail to Set
This parameter determines the period of time that a zone must remain open, following the start of the setting
procedure, before the Fail Set outputs activate. The programmable range is 0–999 seconds; the default is
360 .
NOTE: The Fail to Set countdown time begins as soon as the setting procedure is started.
NOTE: The Fail to Set time should be at a minimum 5 seconds longer than the Exit Time (option 51.04),
to allow for the setting period to expire.
This parameter can be assigned a different value for each group.
36 = Battery Size
Enter the size of the standby battery on the control Panel PSU. The programmable range is 0–99Ah; the
default is 0.
37 = Standby Time
Enter the value (in hours) that the system is required to run on standby battery if there is a mains fail. The
programmable range is 0–99 hours; the default is 0.
The Control Panel PSU calculates the battery run time from the programmed Battery Size (parameter 36)
and the load current. If the programmed Standby Time exceeds the calculated battery run time, a
STANDBY TIME LOW message is displayed on the keypad on attempting to exit engineer mode. Exiting
engineer mode is prevented until a Standby Time that is less than the calculated battery time is entered or a
larger battery is installed in the system and the new battery size is entered in the Battery Size parameter.
To view the latest battery Standby Time refer to Option 61.1.4=Diagnostics.Latest.PSU Comms.
NOTE: The calculated battery run time has a 10% safety margin built in.
38 = ATM Delay
This parameter determines the period of time before the selected ATM zone type is omitted following the
entry of one of the ATM codes. The programmable range is 0–30 minutes; the default ATM Delay is 5.
39 = ATM Timeout
This parameter determines the period of time that the selected ATM zone type is omitted following the entry
of one of the ATM codes. The programmable range is 1–90 minutes; the default ATM Timeout is 30.