IDEC HR6S Series Original Instructions Manual page 68

Safety module
Hide thumbs Also See for HR6S Series:
Table of Contents

Advertisement

Functions
Configuring the Start Function
The start function is configured by means of the start function selector.
Position of start function selector
1
2
3
4
5
6
7
8
A start function with dynamization is typically if the start input is connected to a start push-button.
A start function without dynamization is typically used if the start input is connected to a logic
controller. Refer to the chapter Dynamization
68
Configured start function
Automatic/manual start (depends on
sensor/device connected to start input)
Without startup test
With dynamization
Automatic/manual start (depends on
sensor/device connected to start input)
With startup test
With dynamization
Monitored start
Without startup test
With dynamization
Monitored start
With startup test
With dynamization
Automatic/manual start (depends on
sensor/device connected to start input)
Without startup test
Without dynamization
Automatic/manual start (depends on
sensor/device connected to start input)
With startup test
Without dynamization
Monitored start
Without startup test
Without dynamization
Monitored start
With startup test
Without dynamization
(see page
42) for details.