IDEC HR6S Series Original Instructions Manual page 40

Safety module
Hide thumbs Also See for HR6S Series:
Table of Contents

Advertisement

Engineering
One safety-related input with two input channels with antivalent behavior (magnetic switch with NO
at S12 and NC at S13):
If the level at terminal S12 is logically 0 and the level at terminal S13 is logically 1, the safety-related
input is activated.
Timing diagram for one safety-related input with two input channels with antivalent behavior:
1 = Activation, transition to operating state Run: Outputs Energized
2 = Deactivation, transition to operating state Run: Outputs Deenergized (defined safe state)
Truth table for one safety-related input with two input channels with antivalent behavior:
Signal State
at S12
0
1
Identical signal states are only permissible within the synchronization time
Otherwise, identical signal states trigger an alert.
The truth table applies to the wiring diagrams presented for the application functions.
If the magnetic switch in the wiring example above is used for guard monitoring, this means that
the magnetic switch is presented in the activated state and the guard is closed.
Consult the manual of the sensor/device you want to use for your application function for details
on signal state required for activation and deactivation as defined in the present document.
40
Signal State
Activation State and Operating State
at S13
1
Safety-related input channel activated, operating state Run: Outputs
Energized
0
Safety-related input channel deactivated, operating state Run: Outputs
Deenergized
(see page
35)
(see page
HR9Z-B2190 8/2020
41) .