8 - DIAGNOSTICS

8.6 - Alarms description

The alarm codes are displayed in the Reset Alarms menu, while
in the Current Alarm menu and alarm histories textual information
regarding the event is provided.
8.6.1 - Alarm codes
Jbus
Code
Alarm description
code
Thermistor failure
1
15001
Cooler Entering Fluid Thermistor
2
15002
Cooler Leaving Fluid Thermistor
3
15006
Condenser Entering Fluid Thermistor
4
15007
Condenser Leaving Fluid Thermistor
5
15011
MASTER/Slave Common Fluid Thermistor
6
15012
Circuit A Suction Gas Thermistor
7
15013
Circuit B Suction Gas Thermistor
9
15015
Circuit A Discharge Gas Thermistor
10
15016
Circuit B Discharge Gas Thermistor
12
15018
Circuit A Condenser Subcooling Liquid Thermistor As above
13
15019
Circuit B Condenser Subcooling Liquid Thermistor As above
14
15021
Space Temperature Thermistor
15
15024
Circuit A Economizer Gas Thermistor
16
15025
Circuit B Economizer Gas Thermistor
Transducer failure
18
12001
Circuit A Discharge Transducer
19
12002
Circuit B Discharge Transducer
21
12004
Circuit A Suction Transducer
22
12005
Circuit B Suction Transducer
24
12010
Circuit A Oil Pressure Transducer
25
12011
Circuit B Oil Pressure Transducer
27
12013
Circuit A Economizer Pressure Transducer
28
12014
Circuit B Economizer Pressure Transducer
Communication failure
30
4101
Loss of communication with Compressor Board A
31
4201
Loss of communication with Compressor Board B As above
33
4901
Loss of communication with SIOB/CIOB Board A
34
4902
Loss of communication with SIOB/CIOB Board B
Loss of communication with SIOB/CIOB Board
36
4906
Energy Management
Loss of communication with SIOB/CIOB Board
37
4907
EXV DGT Management
Loss of communication with AUX Board
38
4501
(leak detection optional board)
Process failure and other
39
10001
Cooler Freeze Protection 
40
10002
Circuit A Condenser Freeze Protection
41
10003
Circuit B Condenser Freeze Protection
43
10005
Circuit A Low Suction Temperature
44
10006
Circuit B Low Suction Temperature
46
10008
Circuit A High Superheat
47
10009
Circuit B High Superheat
46
Possible cause
Action taken
Defective thermistor
Unit shuts down
As above
Unit shuts down
As above
None (alert)
As above
None (alert)
Master/Slave assembly
is disabled and the unit
As above
returns to the stand-
alone mode
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
None (alert)
None (alert)
As above
None (alert)
Economizer function
As above
disabled
As above
As above
Defective transducer
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
Bus installation fault,
Circuit A shuts down
communication error
Circuit B shuts down
As above
Unit shuts down
As above
Unit shuts down
As above
Unit shuts down
As above
Unit shuts down
As above
None (alert)
No water flow, defective 
Unit shuts down
thermistor
Discharge pressure
transducer defective,
Circuit A shuts down, but
refrigerant leak or low
the pump is running
condenser water
temperature
Circuit B shuts down,
As above
but the pump is running
Pressure sensor
defective, EXV blocked or
Circuit A shuts down
lack of refrigerant
As above
Circuit B shuts down
Pressure sensor
defective, EXV blocked or
Circuit A shuts down
lack of refrigerant
As above
Circuit B shuts down
Reset type
Automatic, if thermistor
reading returns to normal
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
Automatic, if sensor voltage
reading returns to normal
As above
As above
As above
As above
As above
As above
As above
Automatic, if communication
is re-established
As above
As above
As above
As above
As above
As above
Manual
Automatic (if saturated
discharge temperature is
above 4.4°C); otherwise
Manual
As above
Automatic (the first alarm 
within 24 hours); otherwise
Manual
As above
Manual
Manual