6 - STANDARD CONTROL OPERATIONS AND OPTIONS

6.17 - Trending

This function enables to visualise the operations of the unit and
monitor a set of selected parameters.
To display trends
1. Go to the Main menu.
2. Select Trendings (TRENDING).
3. Select parameters to be displayed and press the Save button
in the lower-left part of the screen.
4. Press the Trending button
trends for the set of selected parameters.
■ Press
to navigate across the timeline or press
to go to the beginning or the end of the selected period.
■ Press the Zoom in button
the Zoom out button
■ Press the Refresh button
NOTE: The 7" touch screen can display 10 points instead of
4 on the graph.
to display the graph showing
to magnify the view or
to expand the viewed area.
to reload data.
For web interface only:
■ Set the time range (start/end dates and time) at the bottom of
the Trendings Plot screen and press the Arrow button
the right side to display the graph showing the performance of
the unit within a selected period of time.

6.18 - User quick test

The Quick Test functionality allows users to test and verify if certain
components of the unit behave correctly (only logged-in users can
activate the Quick Test).
To enable Quick Test
1. Navigate to the Main menu.
2. Select Quick Test 1 (QCK_TST1). The menu can be accessed
when logged in at user access level.
3. Set Quick test Enable [QCK_TEST] to "on".
Quick test Enable [QCK_TEST]
Off/On
On
IMPORTANT: To enable the Quick Test functionality, the unit
must be stopped (Local off mode).
Once the Quick Test functionality is enabled, it is possible to test
parameters  such  as  valves,  pumps'  commands,  etc.  For  more 
details, please see the Quick Test 1 table description (QCK_TST1
– Quick Test 1) in section 5.1.

6.19 - BACnet (option 149)

The BACnet/IP communication protocol is used by the building
management system or the programmable controllers to
communicate with the SmartVu
NOTE: This option requires the Software Activation Key
(see section 6.21).

6.20 - Modbus (option 149B)

The Modbus communication protocol is used by the building
management system or the programmable controllers to
communicate with the SmartVu
NOTE: This option requires the Software Activation Key
(see section 6.21).
control.
TM
control.
TM
on
41