7 - WEB CONNECTION

7.1 - Web interface

The SmartVu
control provides the functionality to access and
TM
control unit parameters from a web interface. To connect to the
controller via the web interface, it is necessary to know the IP
address of the unit.
To verify unit IP address
1. Go to the System menu.
2. Select Network (NETWORK).
3. Verify TCP/IP Address for "IP Network Interface J5 for 4.3-inch
or J15 for 7-inch (eth0)" and "IP Network Interface J16 (eth1)".
See also section 3.2.
■ Unit default address:
169.254.1.1 (J5 / J15, eth0)
192.168.100.100 (J16, eth1) - (only for 7" touch screen)
■ The unit IP address can be changed in the Network table
in the System menu (see section 5.6).
To access SmartVu
web interface
TM
1. Open the web browser.
2. Enter the IP address of the unit in the address bar of the web
browser. Start with https:// followed by the unit IP address.
Example: https://169.254.1.1
3. Press Enter.
4. The web interface will be loaded.
IMPORTANT: Three users can be connected simultaneously
with no priority between them. The last modification is always
taken into account.
Minimum web browser configuration:
■ Internet Explorer (version 11 or higher)
■ Mozilla Firefox (version 60 or higher)
■ Google Chrome (version 65 or higher)
For security reasons the unit cannot be started / stopped via the 
web interface. All other operations, including monitoring unit
parameters or unit configuration, can be performed via the web 
browser interface.
Make sure that your network is protected from malicious
attacks and any other security threats. Do not provide open
access without proper network security safeguards.
The Manufacturer does not hold any responsibility
or liability for damage caused by security breach.
44

7.2 - Technical documentation

When using the SmartVu
TM
may easily access all technical documents related to the product
and its components.
Once you connect to the SmartVu
documentation button
related to the unit.
Technical documentation includes the following documents:
■ Spare parts documentation: The list of spare parts included in
the unit with reference, description and drafting.
■ Misc: Documents such as electrical plans, dimension plans,
unit certificates.
■ PED: Pressure Equipment Directive.
■ IOM: Installation operation and maintenance manual, controls
installation/maintenance manual.
Click the Help button
Modbus user guide and Open Source Licenses used by SmartVu
IMPORTANT: Please save all data (documents, drawings,
diagrams, etc.), for example, on your computer. If display
memory is erased or the display is replaced, all documents
will be lost. Make sure that all documents are stored and may
be accessed at any time.
control via a PC web browser, you
control, click the Technical
TM
in order to see a list of documents
to get access to BACnet user guide,
.
TM