Carrier AquaForce 61XWHZE Control Manual page 19

Smartvu control
Table of Contents

Advertisement

5 - USER INTERFACE: MENU STRUCTURE
SETPOINT – Setpoint Table (continued)
No. Name
Status
35.0 to 85.0
6
hsp2
95.0 to 185.0
0.1 to 11.1
7
hramp_sp
0.2 to 20.0
3.9 to 50.0
8
cauto_sp
39.0 to 122.0
0 to 46.1
9
hauto_sp
32.0 to 115.0
26.7 to 60.0
10 w_sct_sp
80.0 to 140.0
11
lim_sp1
0 to 100
12 lim_sp2
0 to 100
13 lim_sp3
0 to 100
*Depends on the selected language (English by default).
QCK_TST1 – Quick Test 1
No. Name
Status
1
QCK_TEST off/on
2
3
Q_EXVA
0 to 100
4
Q_EXVB
0 to 100
5
Q_EXVC
0 to 100
6
Q_ECO_A
0 to 100
7
Q_ECO_B
0 to 100
8
Q_ECO_C
0 to 100
9
Q_OILS_A
off/on
10 Q_SLI_1A
off/on
11
Q_SLI_2A
off/on
12 Q_OILS_B
off/on
13 Q_SLI_1B
off/on
14 Q_SLI_2B
off/on
15 Q_OILS_C
off/on
16 Q_SLI_1C
off/on
17 Q_SLI_2C
off/on
18 Q_PMP1
0 to 2
19 Q_PMP2
0 to 2
20 Q_HPMP1
0 to 2
21 Q_ELBOXF off/on
22 Q_READY
off/on
23 Q_RUN
off/on
24 Q_CATO
0 to 100
25 Q_RUN_A
off/on
26 Q_RUN_B
off/on
27 Q_RUN_C
off/on
28 Q_SHUT
off/on
Default
Unit
Displayed text*
70.0
°C
Heating Setpoint 2
158.0
°F
0.6
^C
Heating Ramp Loading
1.0
^F
23.9
°C
Cool Changeover Setpt
75.0
°F
17.8
°C
Heat Changeover Setpt
64.0
°F
35.0
°C
Water Val Condensing Stp
95.0
°F
100
%
Switch Limit Setpoint 1
100
%
Switch Limit Setpoint 2
100
%
Switch Limit Setpoint 3
Default
Unit
Displayed text*
off
-
Quick Test Enable
0
%
Circuit A EXV Position
0
%
Circuit B EXV Position
0
%
Circuit C EXV Position
0
%
Circuit A Eco EXV Pos
0
%
Circuit B Eco EXV Pos
0
%
Circuit C Eco EXV Pos
-
-
Circuit A Oil Solenoid
-
-
Circuit A Slide Valve 1
-
-
Circuit A Slide Valve 2
-
-
Circuit B Oil Solenoid
-
-
Circuit B Slide Valve 1
-
-
Circuit B Slide Valve 2
-
-
Circuit C Oil Solenoid
-
-
Circuit C Slide Valve 1
-
-
Circuit C Slide Valve 2
-
-
Cooler Pump 1
-
-
Cooler Pump 2
-
-
Condenser Pump 1
-
-
Electrical Box Fan
-
-
Chiller Ready Output
-
-
Chiller Running Output
0
%
Chiller Capacity in0-10V
-
-
Cir A Running Output
-
-
Cir B Running Output
-
-
Cir C Running Output
-
-
Shutdown Relay Status
Description
Heating setpoint 2 (used during unoccupied periods)
Heating ramp loading setpoint (rate at which the water
temperature may change within one minute in Heating)
Not applicable to this unit
Not applicable to this unit
Water valve condensing setpoint
Switch limit setpoint 1 (demand limit)
Switch limit setpoint 2 (demand limit)
Switch limit setpoint 3 (demand limit)
Description
This parameter is used to enable the Quick Test functionality
(Quick test Enable = yes)
With Quick Test enabled: Forcing a specific parameter given in this 
table allows the user to verify if the component behaves correctly
EXV position, circuit A (100% = EXV fully open)
EXV position, circuit B (100% = EXV fully open)
Not applicable to this unit
Economizer EXV position, circuit A
(100% = Economizer EXV fully open)
Economizer EXV position, circuit B
(100% = Economizer EXV fully open)
Not applicable to this unit
Oil solenoid valve, circuit A
Slide valve 1, circuit A
Slide valve 2, circuit A
Oil solenoid valve, circuit B
Slide valve 1, circuit B
Slide valve 2, circuit B
Not applicable to this unit
Not applicable to this unit
Not applicable to this unit
Cooler pump 1 test:
1 = Pump shall run for a short period of time
2 = Pump shall run all the time (set the value to "0" to stop the
pump test)
Cooler pump 2 test:
1 = Pump shall run for a short period of time
2 = Pump shall run all the time (set the value to "0" to stop the
pump test)
Condenser pump test:
1 = Pump shall run for a short period of time
2 = Pump shall run all the time (set the value to "0" to stop the
pump test)
Electrical box fan
Chiller ready output
Chiller running output
Chiller capacity in 0-10V
Running output, circuit A
Running output, circuit B
Not applicable to this unit
Shutdown relay status
19