Carrier AquaForce 61XWHZE Control Manual page 18

Smartvu control
Table of Contents

Advertisement

5 - USER INTERFACE: MENU STRUCTURE
RUNTIME – Run Times
No. Name
Status
1
HR_MACH
-
2
st_mach
-
3
hr_cp_a
-
4
st_cp_a
-
5
hr_cp_b
-
6
st_cp_b
-
7
hr_exv_a
-
8
hr_exv_b
-
9
hr_cpum1
-
10 hr_cpum2
-
11
hr_hpum1
-
12 hr_hpum2
-
*Depends on the selected language (English by default).
MODES – Modes
No. Name
Status
1
m_delay
no/yes
2
m_2stpt
no/yes
3
m_reset
no/yes
4
m_demlim
no/yes
5
m_ramp
no/yes
6
m_pmprot
no/yes
7
m_pmpper
no/yes
8
m_night
no/yes
9
m_slave
no/yes
10 m_autoc
no/yes
11
m_lowEwt
no/yes
12 m_cpmpro
no/yes
13 m_cpmppr
no/yes
14 m_ice
no/yes
15 m_sst_a
no/yes
16 m_sst_b
no/yes
17 m_sst_c
no/yes
18 m_map_a
no/yes
19 m_map_b
no/yes
20 m_map_c
no/yes
21 m_hp_a
no/yes
22 m_hp_b
no/yes
23 m_hp_c
no/yes
*Depends on the selected language (English by default).
SETPOINT – Setpoint Table
No. Name
Status
-12.0 to 55.0
1
csp1
10.4 to 131.0
-12.0 to 55.0
2
csp2
10.4 to 131.0
-28.9 to 26.0
3
ice_sp
-20.0 to 78.8
0.1 to 11.1
4
cramp_sp
0.2 to 20.0
35.0 to 85.0
5
hsp1
95.0 to 185.0
18
Unit
Displayed text*
hour
Machine Operating Hours
-
Machine Starts Number
hour
Compressor A Hours
-
Compressor A Starts
hour
Compressor B Hours
-
Compressor B Starts
hour
EXV A Hours
hour
EXV B Hours
hour
Cooler Pump #1 Hours
hour
Cooler Pump #2 Hours
hour
Condenser Pump #1 Hours
hour
Condenser Pump #2 Hours
Unit
Displayed text*
-
Start Up Delay In Effect
-
Second Setpoint In Use
-
Reset In Effect
-
Demand limit Active
-
Ramp Loading Active
-
Cooler Pump Rotation
-
Pump Periodic Start
-
Night Low Noise Active
-
Master Slave Active
-
Auto Changeover Active
-
Heating Low EWT Lockout
-
Condenser Pump Rotation
-
Cond Pump Periodic Start
-
Ice Mode In Effect
-
Low Suction Circuit A
-
Low Suction Circuit B
-
Low Suction Circuit C
-
Map compressor Circuit A
-
Map compressor Circuit B
-
Map compressor Circuit C
-
High Pres Override Cir A
-
High Pres Override Cir B
-
High Pres Override Cir C
Default
Unit
Displayed text*
20.0
°C
Cooling Setpoint 1
68.0
°F
20.0
°C
Cooling Setpoint 2
68.0
°F
6.7
°C
Cooling Ice Setpoint
44.0
°F
0.6
^C
Cooling Ramp Loading
1.0
^F
70.0
°C
Heating Setpoint 1
158.0
°F
Description
Machine operating hours
Number of machine starts
Operating hours, compressor A
Number of starts, compressor A
Operating hours, compressor B
Number of starts, compressor B
Operating hours, EXV (circuit A)
Operating hours, EXV (circuit B)
Operating hours, cooler pump 1
Operating hours, cooler pump 2
Operating hours, condenser pump
Not applicable to this unit
Description
Start-up delay in effect
Second setpoint in use
Setpoint reset active
Demand limit active
Ramp loading active
Cooler pump rotation
Pump periodic start active
Night low noise active
Master/Slave mode active
Not applicable to this unit
Heating low EWT lockout
Not applicable to this unit
Condenser pump periodic start
Ice storage mode active (EMM option)
Low suction, circuit A
Low suction, circuit B
Not applicable to this unit
Compressor mapping, circuit A
Compressor mapping, circuit B
Not applicable to this unit
High pressure override, circuit A
High pressure override, circuit B
Not applicable to this unit
Description
Cooling setpoint 1 (used during occupied periods)
Cooling setpoint 2 (used during unoccupied periods)
Cooling ice setpoint
Cooling ramp loading setpoint (rate at which the water
temperature may change within one minute in Cooling)
Heating setpoint 1 (used during occupied periods)

Advertisement