Network Menu - Carrier AquaForce 61XWHZE Control Manual

Smartvu control
Table of Contents

Advertisement

5 - USER INTERFACE: MENU STRUCTURE

5.5 - Network menu

The Network menu allows the user to change network setting for
BACnet/Modbus and define e-mail accounts used for alarm
notifications (see section 8.3).
NETWORK – Network Menu
Icon
Name
MODBUSRS
MODBUSIP
BACnet
EMAILCFG
*Depends on the selected language (English by default).
MODBUSRS – ModbusRTU Config.
No. Name
Status
1
modrt_en
no/yes
2
ser_UID
1 to 247
3
metric
no/yes
4
swap_b
0 to 1
5
6
7
baudrate
0 to 2
8
9
10
11 parity
0 to 2
12
13
14
15 stop_bit
0 to 1
16
17
18 real_typ
0 to 1
19
20
21 reg32bit
0 to 1
22
23
*Depends on the selected language (English by default).
MODBUSIP – ModbusTCP/IP Config.
No. Name
Status
1
modip_en
no/yes
2
ser_UID
1 to 247
3
port_nbr
0 to 65535
4
metric
no/yes
5
swap_b
0 to 1
6
26
Displayed text*
ModbusRTU Config.
ModbusTCP/IP Config.
BACnet Parameters
Email Configuration
Default
Unit
Displayed text*
no
-
RTU Server Enable
1
-
Server UID
yes
-
Metric Unit
0
-
Swap Bytes
0 = Big Endian
1 = Little Endian
0
-
Baudrate
0 = 9600
1 = 19200
2 = 38400
0
-
Parity
0 = No Parity
1 = Odd Parity
2 = Even Parity
0
-
Stop bit
0 = One Stop Bit
1 = Two Stop Bits
1
-
Real type management
0 = Float X10
1 = IEEE 754
1
-
Enable 32 bits registers
0 = IR/HR in 16 bit mode
1 = IR/HR in 32 bit mode
Default
Unit
Displayed text*
no
-
TCP/IP Server Enable
1
-
Server UID
502
-
Port Number
yes
-
Metric Unit
0
-
Swap Bytes
0 = Big Endian
NOTE: If you need to add an option (BACnet/Modbus), please
contact your local service representative.
Description
Modbus RTU configuration
Modbus TCP/IP configuration
BACnet standard configuration
Email settings
Description
RTU Server Enable
Server UID
Metric Unit
Swap Bytes
0 = Big Endian
1 = Little Endian
Baudrate
0 = 9600
1 = 19200
2 = 38400
Parity
0 = No Parity
1 = Odd Parity
2 = Even Parity
Stop bit
0 = One Stop Bit
1 = Two Stop Bits
Real type management
0 = Float X10
1 = IEEE 754
Enable 32 bits registers
0 = IR/HR in 16 bit mode
1 = IR/HR in 32 bit mode
Description
TCP/IP Server Enable
Server UID
Port Number
Metric Unit
Swap Bytes
0 = Big Endian