8 - DIAGNOSTICS
Jbus
Code
Alarm description
code
49
10011
Circuit A Low Superheat
50
10012
Circuit B Low Superheat
Customer Interlock Failure 
52
10014
(applies to units with EMM option)
53
10028
Electrical Box Thermostat
54
10029
Loss of communication with System Manager
55
10030
Master/Slave communication Failure 
56
10067
Circuit A Low Oil Pressure
57
10068
Circuit B Low Oil Pressure
59
10070
Circuit A Max Oil Filter Differential Pressure 
60
10071
Circuit B Max Oil Filter Differential Pressure 
62
10084
Circuit A High Oil Filter Drop Pressure 
63
10085
Circuit B High Oil Filter Drop Pressure 
65
10075
Circuit A Low Oil level
66
10076
Circuit B Low Oil level
Configuration failure
68
9001
Master/Slave configuration error 
69
8000
Initial factory configuration required
70
7001
Illegal configuration
105
8001
Illegal Brand Identifier
Process failure and other (cont.)
71
10031
Unit is in CCN emergency stop
72
10032
Cooler pump #1 fault
73
10033
Cooler pump #2 fault
74
10015
Condenser Flow Switch Failure 
Circuit A High condensing temperature out of map
75
10037
compressor
Circuit B High condensing temperature out of map
76
10038
compressor
80
10078
Circuit A High Discharge Gas Temperature
81
10079
Circuit B High Discharge Gas Temperature
Circuit A Low economizer pressure or Suction
83
10081
valve closed
Circuit B Low economizer pressure or Suction
84
10082
valve closed
86
10087
Circuit A Slide Valve Control Unverifiable 
87
10088
Circuit B Slide Valve Control Unverifiable 
89
10090
Cooler Flow Switch Setpoint Configuration Failure 
Possible cause
Action taken
As above
Circuit A shuts down
As above
Circuit B shuts down
Customer interlock closed Unit shuts down
Electrical box fault:
Control box poorly
Unit shuts down
ventilated or poor
electrical connection
CCN bus installation
Unit returns to the
defective
stand-alone mode
Communication between
Master/slave control
the Master and the Slave
disabled
unit is lost
Pressure sensor fault,
defective wiring or oil filter 
Circuit A shuts down
installation fault
As above
Circuit B shuts down
The affected 
compressor is stopped,
As above
the second compressor
continues to run
As above
As above
As above
Circuit A shuts down
As above
Circuit B shuts down
Oil level too low or oil
Circuit A shuts down
level detector defective
As above
Circuit B shuts down
Master/slave operation
is disabled and the unit
Configuration failure
returns to the stand-
alone mode
No factory configuration
Unit cannot be started
Incorrect unit configuration Unit cannot be started
Incorrect unit configuration Unit cannot be started
Network emergency stop
Unit shuts down
command
Unit is restarted with
Pump overheats or poor
another pump running.
pump connection
If no pump is available,
the unit shuts down
As above
As above
Condenser flow switch is 
Condenser pump is
open
stopped, Unit shuts down
Defective transducer
None (alert)
As above
None (alert)
Defective transducer, max.
condensing temperature
Circuit A shuts down
setpoint too low or
refrigerant charge too high
As above
Circuit B shuts down
Economizer pressure
transducer defective,
Circuit A shuts down
suction valve fault
As above
Circuit B shuts down
Defective or incorrectly
wired solenoid valves,
None (alert)
defective current
transformer
As above
None (alert)
Defective flow controller 
Unit is not allowed to
or wiring error
start
Reset type
Manual
Manual
Automatic (the first alarm 
within 24 hours) or Manual
Automatic, if the safety
input is closed
Automatic, if communication
is re-established
Automatic, if communication
is re-established
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Automatic, if master/slave
configuration returns to 
normal or the unit returns
to stand-alone mode
Automatic, if configuration 
is provided
Automatic, if configuration 
is corrected
Automatic, if configuration 
is corrected
Automatic, if operating
conditions return to normal
Manual
Manual
Automatic (the first alarm 
within 24 hours); otherwise
Manual
Automatic
Automatic
Manual
Manual
Manual
Manual
Manual
Manual
Manual
47