Carrier AquaForce 61XWHZE Control Manual page 20

Smartvu control
Table of Contents

Advertisement

5 - USER INTERFACE: MENU STRUCTURE
QCK_TST1 – Quick Test 1 (continued)
No. Name
Status
29 Q_ALARM
off/on
30 Q_ALERT
off/on
31 Q_DEXV_A 0 to 100
32 Q_DEXV_B 0 to 100
33 Q_3W_VLV 0 to 100
*Depends on the selected language (English by default).
IMPORTANT: To enable the Quick Test functionality, the unit
must be stopped (Local off mode).
Trendings
No. Name
1
GENUNIT_CTRL_PNT
2
TEMP_COOL_EWT
3
TEMP_COOL_LWT
4
TEMP_COND_EWT
5
TEMP_COND_LWT
6
TEMP_SCT_A
7
TEMP_SST_A
8
TEMP_SCT_B
9
TEMP_SST_B
10 INPUTS_CURREN_A
11
INPUTS_CURREN_B
12 EXV_CTRL_EXV_A
13 EXV_CTRL_DSH_A
14 EXV_CTRL_ov_exv_a
15 EXV_CTRL_EXV_B
16 EXV_CTRL_DSH_B
17 EXV_CTRL_ov_exv_b
18 EXV_CTRL_eco_sha
19 EXV_CTRL_ov_eco_a
20 EXV_CTRL_eco_shb
21 EXV_CTRL_ov_eco_b
22 LOADFACT_cap_t_a
23 LOADFACT_cap_t_b
24 LOADFACT_smz
25 LOADFACT_over_cap
*Depends on the selected language (English by default).
OPT_STA – Software Options
No. Name
Status
1
opt5
no/yes
2
opt6
no/yes
3
opt149
no/yes
4
opt149B
no/yes
5
opt295
no/yes
*Depends on the selected language (English by default).
20
Default
Unit
Displayed text*
-
-
Alarm Relay Status
-
-
Alert Relay Switch
0
%
DGT EXV Position A
0
%
DGT EXV Position B
-
%
3 way valve position
Status
Unit
-
%
-
°C/°F
-
°C/°F
-
°C/°F
-
°C/°F
-
°C/°F
-
°C/°F
-
°C/°F
-
°C/°F
-
AMPS
-
AMPS
-
%
-
^C/^F
-
-
-
%
-
^C/^F
-
-
-
^C/^F
-
-
-
^C/^F
-
-
-
%
-
%
-
%
-
-
Unit
Displayed text*
-
OPT5: Medium Brine
-
OPT6: Low Brine
-
OPT149: BACnet
-
OPT149B: Modbus
-
OPT295: Fast Capacity Recovery Not applicable to this unit
Description
Alarm relay status
Alert relay switch
DGT EXV position, circuit A (100% = EXV fully open)
DGT EXV position, circuit B (100% = EXV fully open)
3-way valve position
Description
Control point
Cooler entering fluid 
Cooler leaving fluid 
Condenser entering fluid
Condenser leaving fluid
Saturated condensing temperature, circuit A
Saturated suction temperature, circuit A
Saturated condensing temperature, circuit B
Saturated suction temperature, circuit B
Motor current, circuit A
Motor current, circuit B
EXV position, circuit A
Discharge superheat, circuit A
EXV override, circuit A
EXV position, circuit B
Discharge superheat, circuit B
EXV override, circuit B
Economizer superheat, circuit A
EXV override, circuit A
Economizer superheat, circuit B
EXV override, circuit B
Actual capacity, circuit A
Actual capacity, circuit B
Load/unload factor
Active capacity override
Description
Not applicable to this unit
Not applicable to this unit
Parameter set to "yes" means that BACnet option which requires the
Software Key is activated (see also section 6.19)
Parameter set to "yes" means that Modbus option which requires the
Software Key is activated (see also section 6.20)