5 - USER INTERFACE: MENU STRUCTURE
INPUTS – Inputs Status (continued)
No. Name
Status
13 REM_LOCK
open/close
14 ICE_SW
open/close
15 OCC_OVSW open/close
16 LIM_ANAL
-
17 ELEC_BOX
open/close
18 leak_v
-
19 leak_2_v
-
20 ElBxF1_s
off/on
*Depends on the selected language (English by default).
OUTPUTS – Outputs Status
No. Name
Status
1
COMP_A
off/on
2
OIL_SL_A
off/on
3
SLID_1_A
off/on
4
SLID_2_A
off/on
5
CAPT010A
-
6
COMP_B
off/on
7
OIL_SL_B
off/on
8
SLID_1_B
off/on
9
SLID_2_B
off/on
10 CAPT010B
-
11
COMP_C
off/on
12 OIL_SL_C
off/on
13 SLID_1_C
off/on
14 SLID_2_C
off/on
15 CAPT010C
-
16 CAPT_010
-
17 ALARM
off/on
18 RUNNING
off/on
19 ALERT
off/on
20 SHUTDOWN off/on
21 pos_3wv
0 to 100%
22 READY
off/on
23 ElBxFan
off/on
*Depends on the selected language (English by default).
PUMPSTAT – Pump Status
No. Name
Status
1
SET_FLOW
no/yes
2
CPUMP_1
off/on
3
CPUMP_2
off/on
4
ROTCPUMP no/yes
5
FLOW_SW
open/close
6
HPUMP_1
off/on
7
HPUMP_2
off/on
8
ROTHPUMP no/yes
9
CONDFLOW open/close
*Depends on the selected language (English by default).
Unit
Displayed text*
-
Customer Interlock
-
Ice Done Storage Switch
-
Occupied Override Switch
mA
Limit 4-20mA Signal
-
Electrical Box Interlock
V
Leakage detector 1 val
V
Leakage detector 2 val
-
ElecBoxFan input state
Unit
Displayed text*
-
Compressor A
-
Oil Solenoid Output A
-
Slide Valve 1 Output A
-
Slide Valve 2 Output A
V
Capacity Signal Cir A
-
Compressor B
-
Oil Solenoid Output B
-
Slide Valve 1 Output B
-
Slide Valve 2 Output B
V
Capacity Signal Cir B
-
Compressor C
-
Oil Solenoid Output C
-
Slide Valve 1 Output C
-
Slide Valve 2 Output C
V
Capacity Signal Cir C
V
Chiller Capacity signal
Alarm Relay Status
Running Relay Status
Alert Relay State
Shutdown Indicator State
%
Cond 3 Way Valve Pos
-
Ready or Running Status
-
Electrical Box Fan sw
Unit
Displayed text*
-
Cooler Flow Setpoint Out
-
Cooler Pump #1 Command
-
Cooler Pump #2 Command
-
Rotate Cooler Pumps ?
-
Cooler Flow Switch
-
Condenser Pump Cmd1
-
Condenser Pump Cmd2
-
Rotate Condenser Pumps ?
-
Condenser Flow Status
Description
Customer interlock: When the contact is closed, the unit will be
stopped with no delay (alarm 10014). The switch is provided on the
customer's terminal block of the optional EMM.
Ice done storage switch
Occupied override switch
4-20 mA signal, capacity limit
Electrical box interlock
Refrigerant leakage detection (optional): Leakage detector 1 value
Refrigerant leakage detection (optional): Leakage detector 2 value
Electrical box fan input state
Description
Compressor A status (circuit A)
Oil solenoid output, circuit A
Slide valve 1 output, circuit A
Slide valve 2 output, circuit A
0-10V capacity signal, circuit A
Compressor B status (circuit B)
Oil solenoid output, circuit B
Slide valve 1 output, circuit B
Slide valve 2 output, circuit B
0-10V capacity signal, circuit B
Not applicable to this unit
Not applicable to this unit
Not applicable to this unit
Not applicable to this unit
Not applicable to this unit
Chiller capacity signal
Alarm relay status
Running relay status
Alert relay state
Shutdown indicator state
Condenser 3-way valve position
Unit ready/running status
Electrical box fan status
Description
Cooler flow setpoint output
Cooler pump 1 control enabled
Cooler pump 2 control enabled
Cooler pumps' rotation
Cooler flow switch
Condenser pump control enabled
Not applicable to this unit
Rotate condenser pumps?
Condenser flow status