5 - USER INTERFACE: MENU STRUCTURE
PUMPCONF – Pump Configuration
No. Name
Status
1
hpumpseq
0 to 1
2
cpumpseq
0 to 4
3
4
5
6
7
8
pump_del
24 to 3000
9
pump_per
no/yes
10 pump_sby
no/yes
11 pump_loc
no/yes
12 stopheat
no/yes
13 stopcool
no/yes
*Depends on the selected language (English by default).
RESETCFG – Reset Configuration
No. Name
Status
1
cr_sel
0 to 4
2
hr_sel
0 to 4
3
4
5
6
7
0 to 13.9
8
dt_cr_no
0 to 25.0
0 to 13.9
9
dt_cr_fu
0 to 25.0
10 v_cr_no
0 to 20
11 v_cr_fu
0 to 20
-10.0 to 51.7
12 spacr_no
14 to 125.0
-10.0 to 51.7
13 spacr_fu
14 to 125.0
-16.7 to 16.7
14 cr_deg
-30.0 to 30.0
15
16
0 to 13.9
17 dt_hr_no
0 to 25.0
0 to 13.9
18 dt_hr_fu
0 to 25.0
19 v_hr_no
0 to 20
20 v_hr_fu
0 to 20
-10.0 to 51.7
21 spahr_no
14 to 125.0
-10.0 to 51.7
22 spahr_fu
14 to 125.0
-16.7 to 16.7
23 hr_deg
-30.0 to 30.0
24 both_sel
no/yes
25 auto_sel
no/yes
*Depends on the selected language (English by default).
Default
Unit
Displayed text*
0
-
Cond. Pumps Sequence
0
-
Cooler Pumps Sequence
0 = No Pump
1 = One Pump Only
2 = Two Pumps Auto
3 = Pump#1 Manual
4 = Pump#2 Manual
48
hour
Pump Auto Rotation Delay
no
-
Pump Sticking Protection
no
-
Stop Pump During Standby
yes
-
Flow Checked If Pump Off
no
-
Cooler Pump Off In Heat
no
-
Cond Pump Off In Cool
Default
Unit
Displayed text*
0
-
Cooling Reset Select
0
-
Heating Reset Select
0=None
2=Delta T, 4=Space Temp
3=4-20mA control
Cooling
0
^C
Delta T No Reset Value
0
^F
0
^C
Delta T Full Reset Value
0
^F
0
mA
Current No Reset Value
0
mA
Current Full Reset Value
-10.0
°C
Space T No Reset Value
14.0
°F
-10.0
°C
Space T Full Reset Value
14.0
°F
0
^C
Cooling Reset Deg. Value
0
^F
Heating
0
^C
Delta T No Reset Value
0
^F
0
^C
Delta T Full Reset Value
0
^F
0
mA
Current No Reset Value
0
mA
Current Full Reset Value
-10.0
°C
Space T No Reset Value
14.0
°F
-10.0
°C
Space T Full Reset Value
14.0
°F
0
^C
Heating Reset Deg. Value
0
^F
no
-
HSM Both Command Select HSM both command selection
no
-
Auto Changeover Select
Description
Condenser pump settings (this unit can control only
one condenser pump)
Cooler pumps' sequence
0 = No pump
1 = One pump only
2 = Two pumps auto (units with two pumps)
3 = Pump 1 selected
4 = Pump 2 selected
Pump auto rotation delay (applies to units with two
pumps and "auto" control enabled, cpumpseq = 2)
Pump anti-sticking protection
Stop pump during standby
Flow checked when the pump is off
Cooler pump OFF in heating
Condenser pump OFF in cooling
Description
Cooling reset selection
Heating reset selection
0 = None
2 = Delta T, 4 = Space Temperature
3 = 4-20 mA control
Cooling
Delta T, no reset value
Delta T, full reset value
Current, no reset value
Current, full reset value
Space temperature, no reset value
Space temperature, full feset value
Maximum cooling reset value
Heating
Delta T, no reset value
Delta T, full reset value
Current, no reset value
Current, full reset value
Space temperature, no reset value
Space temperature, full reset value
Maximum heating reset value
Not applicable to this unit