1-
DESCRIPTION – OPERATION
APPLICATIONS
The condensers in the SOPRANO, ADAGIO, ALTO and TENOR ranges are designed for external installation in all refrigeration and air
conditioning applications.
HFC except R134A : PS = 28 bar.
R134A : PS = 19 bar.
Condensers SV (vertical air flow) must be storage as their running positions, or inside a building, in order that water doesn't go inside
electrical equipements.
BODY
Designed in painted or pre-glazed galvanised sheet metal depending on model. Individual separation of fans in order to optimise the
circulation of air. Hoisting holes on all models.
COIL
The condensers are fitted with one or many coils with profiled aluminium fins and copper tubes.
Refrigeration joints to be welded.
VENTILATION
Motors : dual-speed high resistant rotor.
Motors :
The choice of speed is determined by the choice of Star Delta connection for a given voltage.
This means, for a three-phase voltage of 400V, that the Star or Delta connection may be used (change from low speed to high speed)
only if authorized by PROFROID (see page 8).
On the other hand, the Star connection for old 230V three-phase circuits is forbidden.
Common characteristics of these motors:
Standard Characteristics
Ambient Temperature
Hygrometry
Protection factor with purge holes
sealed (CEI 34-5)
Class (CEI 85 et CEI 34-1).
Electrical supply
Important
: the maximum imbalance between phases is 2% in voltage and 10% in current per motor.
Voltage limits : 400V +7% / -10%
Rotors :
SO50 and SO60 Ranges: rotor with aluminium blades fixed to a steel hub.
SO90, AL91 and TE90 Ranges: rotor with steel blades fixed to a steel hub.
 EC Motors
They are equipped with an electronic switch for continuous speed variation and independently for each motor fan. Those engines are
"synchronous" with higher efficiency than standard motors.
Common characteristics of these motors:
Standard
Characteristics
Ambient Temperature
Protection factor with
purge
holes
sealed
(CEI 34-5)
EC M1
EC M2
Electrical supply
Important
: the maximum imbalance between phases is 2% in voltage and 10% in current per motor.
SOPRANO 50/60
400 V - 50 Hz
SOPRANO 60 / ADAGIO 60
Min. 155 (1V) / Max. 1140 tr
-
380-480 V / 3 / 50-60 Hz
-30 à +45°C
60 à 98 %
IP55
F
SOPRANO 90, ALTO 91, TENOR 90
- 25 / + 60 °C
IP54
Min. 175 (1,4V) / Max. 1000 tr
Min. 111 (1,4V) / Max. 610 tr
ADAGIO 50/60
SOPRANO 90 ALTO 91
-25 à +50°C
60 à 98 %
IP54
F
400 V - 50 Hz
TENOR 90
-30 à +45°C
60 à 98 %
IP55
F
400 V - 50 Hz