Variable Speed Drive LED Location and Description (Sizes 25, 36, 37, 48, 49 and 60)
Reference
Color
LD1
Red
LED1
Red
LED3
Amber
LD5
Green
Reference
Color
STATUS
Amber
COMM
Green
Reference
Color
STATUS
Amber
COMM
Green
Fault Code Description
Communications Loss
NOTE: If any of the AOC control board header pins are damaged or are not making good contact, AOC board should be replaced.
MOC LED Description (Sizes 25, 36, 37, 48, 49 AND 60)
Status
Steady On
MOC powered where DC bus is 40volts or greater
Off
No power, capacitor voltage drained
Steady On
DCF and board DC high voltage and discharge circuit powered on
Off
No power
Steady On
MOC board switching power supply to power AOC board on
Off
No Power
Blinking
Indicates communication from MOC to AOC
Steady On
Indicates 5 volt connection status OK between AOC and MOC
Off
No Power
AOC LED Descriptions (Sizes 25, 36, 37, 48, 49 AND 60)
Status
Steady On
AOC status --- standby mode
Blinking
AOC function/fault status
Steady On
Communication from AOC to indoor wall control
LED Not Functioning Properly --- Requires AOC or Inverter Replacement
Suspect AOC board
If Amber STATUS light is not on (neither steady nor blink-
ing), with power to outdoor unit
In Communicating mode, if Green COMM LED is not on
when AB indoor wires are connected to AOC AB connector
and indoor has communications
UI Fault Codes requiring AOC or Inverter Replacement
AOC STATUS is not functioning properly and AOC board
should be replaced.
AOC is not capable of communicating with indoor; AOC
board should be replaced.
Fault Code
Loss of communication with outdoor unit AOC board;
179
AOC or Inverter may need to be replaced
28
Description
Description
Failure Description
Failure Description