Carrier AquaForce 61XWHZE Control Manual page 49

Smartvu control
Table of Contents

Advertisement

8 - DIAGNOSTICS
8.6.2 - Compressor alarms
The following table presents a list of subcodes associated with
compressor failure.
Jbus
Code** Alarm description
code*
106 (A)
xx01
Compressor Motor temperature too high
125 (B)
107 (A)
xx02
Compressor Motor temperature out of range
126 (B)
108 (A)
xx03
Compressor High pressure switch protection
127 (B)
109 (A)
xx04
Compressor Over current
128 (B)
110 (A)
xx05
Compressor Locked rotor
129 (B)
111 (A)
xx06
Compressor Phase loss L1
130 (B)
112 (A)
xx07
Compressor Phase loss L2
131 (B)
113 (A)
xx08
Compressor Phase loss L3
132 (B)
114 (A)
xx09
Compressor Low current alarm
133 (B)
115 (A)
Compressor Y delta starter current increase failure
xx10
134 (B)
alarm
116 (A)
xx11
Compressor Contactor failure
135 (B)
117 (A)
xx12
Compressor Unable to stop motor
136 (B)
118 (A)
xx13
Compressor Phase reversal
137 (B)
119 (A)
xx14
Compressor MTA configuration fault
138 (B)
120 (A)
xx15
Compressor Configuration switch mismatch
139 (B)
121 (A)
xx16
Compressor Unexpected switch setting change
140 (B)
122 (A)
xx17
Compressor Power on reset
141 (B)
123 (A)
xx18
Compressor UL 1998 critical section software error
142 (B)
124 (A)
Compressor UL 1998 current measure dual channel
xx19
143 (B)
mismatch
* Jbus code: (A) refers to compressor A, (B) refers to compressor B
** Alarm code: XX stands for compressor (11 = compressor A , 21 = compressor B)
Possible cause
Motor/wiring fault
Probe defective or incorrect wiring
Coil fouled, lack of condenser flow, 
condenser valve blocked, fan circuit
fault, high entering air or condenser
water temperature
-
Mechanical compressor fault, motor fault
or defective compressor slide valve
Power supply wiring fault
Power supply wiring fault
Power supply wiring fault
Detective contactor or capacity fault
Incorrect wiring or no power for the delta
contactor
Incorrect wiring or defective contactor or
TCPM board
Incorrect wiring or defective contactor
-
MTA configuration incorrect or defective 
TCPM board
Configuration switch S1 incorrect wiring 
or defective TCPM board
As above
Verify that power supply cuts have
occurred
Power network noise or defective TCPM
board
Power network noise or defective TCPM
board
Action taken
Reset type
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
Unit shuts down
Manual
49

Advertisement

Table of Contents
loading

Table of Contents