6 - STANDARD CONTROL OPERATIONS AND OPTIONS
6.6.1 - Active setpoint
Two setpoints can be selected when the unit is in Heating mode,
and three setpoints can be selected when the unit is in Cooling
mode. The first cooling/heating setpoint is normally used during 
occupied periods and the second cooling/heating setpoint is used
during unoccupied periods, whereas the third cooling setpoint is
used  for  ice  storage  (ice  configuration  and  EMM  SIOB/CIOB 
required).
Mode
Setpoint 1
Setpoint 2
Cooling
Occupied
Unoccupied
Heating
Occupied
Unoccupied
Depending on the current operation type (local/remote/network),
the active setpoint can be selected manually in the Main menu
(Heat/Cool Select, GENUNIT) in Local mode, with the volt-free
user contacts in Remote mode (see also section 3.8), with network
commands in Network mode (CCN, BACnet, Modbus) or
automatically with the setpoint time schedule (schedule 2).
Local operating type
Parameters status
Setpoint
Heating/cooling
selection
operating mode
[sp_sel]
cooling
sp-1
cooling
sp-2
cooling
sp-2
cooling
sp-2
cooling
auto
cooling
auto
cooling
auto
cooling
auto
heating
sp-1
heating
sp-2
heating
auto
heating
auto
Remote operating type
Parameters status
Setpoint
Heating/cooling
selection
operating mode
[sp_sel]
cooling
-
cooling
-
cooling
-
cooling
-
heating
-
heating
-
Network operating type
Parameters status
Setpoint
Heating/cooling
selection
operating mode
[sp_sel]
cooling
-
cooling
-
heating
-
heating
-
*Any configuration, (-) default configuration.
NOTE: Ice storage configuration [Ice_cnfg] and ice done
contact [Ice_done] apply only to units with the optional energy
management module.
Setpoint 3
Ice storage cooling setpoint
-
Ice storage
Ice done contact
configuration
[Ice_done]
[Ice_cnfg]
-
*
no
*
yes
closed
yes
open
-
*
no
*
yes
closed
yes
open
-
*
-
*
-
*
-
*
Ice storage
Ice done contact
configuration
[Ice_done]
[Ice_cnfg]
-
*
no
*
yes
closed
yes
open
-
*
-
*
Ice storage
Ice done contact
configuration
[Ice_done]
[Ice_cnfg]
-
*
-
*
-
*
-
*
The following tables summarise possible selections
depending on the control operating type (Local, Remote or
Network) and the following parameters:
■ Heating or Cooling operating mode: Heat/Cool select
(HC_SEL, GENUNIT menu).
■ Setpoint selected via the SmartVu
the selection of the active setpoint if the unit is in the Local
operating type (SP_SEL, GENUNIT menu)
■ Remote setpoint contacts:
- Ice configuration from the user configuration menu
(GENCONF, Ice_cnfg must be set to "yes").
- Ice done contact from EMM (SIOB/CIOB EMM board,
DI4_ICE_SW, by default set to "closed").
- Dual setpoint switch status (spt_sw).
■ Schedule 2 status: Schedule for setpoint selection
(GENUNIT, SP_OCC set to "yes" or "no").
Setpoint switch
Schedule 2 status
[spt_sw]
[sp_occ]
*
*
*
*
*
occupied
*
unoccupied
*
unoccupied
*
unoccupied
*
*
*
occupied
*
unoccupied
Setpoint switch
Schedule 2 status
[spt_sw]
[sp_occ]
open
closed
closed
closed
open
closed
Setpoint switch
Schedule 2 status
[spt_sw]
[sp_occ]
*
occupied
*
unoccupied
*
occupied
*
unoccupied
user interface: It permits
TM
Active setpoint
-
cooling setpoint 1
-
cooling setpoint 2
-
cooling setpoint 2
-
cooling ice setpoint
cooling setpoint 1
cooling setpoint 2
cooling setpoint 2
cooling ice setpoint
-
heating setpoint 1
-
heating setpoint 2
heating setpoint 1
heating setpoint 2
Active setpoint
-
cooling setpoint 1
-
cooling setpoint 2
-
cooling setpoint 2
-
cooling ice setpoint
-
heating setpoint 1
-
heating setpoint 2
Active setpoint
cooling setpoint 1
cooling setpoint 2
heating setpoint 1
heating setpoint 2
37