5 - USER INTERFACE: MENU STRUCTURE
The Configuration menu gives access to a number of user-
modifiable  parameters  such  as  pump  configuration,  schedule 
menu, etc. The Configuration menu is password-protected.
To access the Configuration menu, press the Main menu button
located in the upper-left part of the Home screen, and then select
Configuration Menu. 
Once all the necessary modifications have been made, press the 
Save button to confirm your changes or the Cancel button to exit
the screen without making modifications.
GENCONF – General Configuration
No. Name
Status
1
lead_cir
0 to 2
2
3
4
seq_typ
0 to 2
5
6
7
ramp_sel
no/yes
8
off_on_d
1 to 15
9
nh_start
00:00
10 nh_end
00:00
11 nh_limit
0 to 100
12 bas_menu
0 to 3
13
14
15
16
17 lim_sel
0 to 2
18
19
20
21 lim_mx
0 to 20
22 lim_ze
0 to 20
23 curr_sel
no/yes
24 curr_ful
0 to 4000
25 ice_cnfg
no/yes
26 al_rever
no/yes
*Depends on the selected language (English by default).
22
Default
Unit
Displayed text*
0
-
Cir Priority Sequence
0=Auto,
1=A Prio
2=B Prio
0
-
Loading Sequence
0 = Equal,
1 = Staged
2 = Smart
no
-
Ramp Loading Select
1
min
Unit Off to On Delay
0
-
Night Mode Start Hour
0
-
Night Mode End Hour
100
%
Night Capacity Limit
0
-
Basic Menu Configuration
0 = All Access
1 = no alarm menu
2 = no setpoint menu
3 = 1 + 2
0
-
Demand Limit Type Select
0 = None
1 = Switch Control
2 = 4-20mA Control
0
mA
mA For 100% Demand Limit 100% demand limit (mA)
10
mA
mA For 0% Demand Limit  
no
-
Current Limit Select
2000
A
CurrentLimit at 100%
no
-
Ice Mode Enable
no
-
Reverse Alarms Relay
System configuration override: In some cases it is possible to
override system configuration. Note that not all parameters can 
be overridden by the control.
CAUTION: Since specific units may not include additional
features, some tables may contain parameters that cannot be
configured for a given unit.
Description
Circuit priority sequence
0 = Automatic circuit selection
1 = Circuit A priority
2 = Circuit B priority
Loading sequence (see also section 6.12)
0 = Equal loading sequence
1 = Staged loading sequence
2 = Smart loading sequence
Ramp loading selection
Unit off to on delay
Night mode start time
Night mode end time
Night capacity limit
Basic menu configuration
0 = All access
1 = No alarm menu
2 = No setpoint menu
3 = No alarm and no setpoint menu
Demand limit selection
0 = None
1 = Switch control
2 = 4-20 mA control
0% demand limit (mA)
Current limit selection
Current limit at 100%
Ice mode enabled
Alarm / Alert signals reverted
No = standard operation
Yes = alarm/alert/shutdown outputs are "On" even if
there is no alarm/alert (alarm output unavailable)