8 - DIAGNOSTICS
Jbus
Code
Alarm description
code
90
10091
Cooler Flow Switch Failure 
91
10100
Electrical Box Fan Failure
92
10097
Water Exchanger Temperature Sensors Swapped
Maintenance alarms
93
13001
Service Maintenance Alert
Fgas check needed, call your maintenance 
94
13005
company
Software failure
95
55001
Database Module Failure
96
56001
Lenscan Module Failure
Device failure
97
57020
Main EXV stepper motor Failure – cir A
98
57021
Main EXV stepper motor Failure – cir B
100
57023
EXV eco stepper motor Failure – cir A
101
57024
EXV eco stepper motor Failure – cir B
103
10050
Refrigerant Leakage Detection
Replacement mode: Software activation key(s) missing
Replacement Mode: please contact Service
104
10122
Representative to activate options
Compressor failure
106
11nn
Compressor A fault
– 124
125
21nn
Compressor B fault
– 143
48
Possible cause
Action taken
Compressors and the
Cooler flow switch is open
evaporator pump are
stopped
Electrical box fan
malfunction or fan current
Unit shuts down
probe malfunction
Leaving water temperature
is higher than entering
Unit shuts down
water temperature
Preventive maintenance
date has passed;
servicing action required;
None (alert)
please contact your local
service representative
As above
None (alert)
Software problem, Please
contact your local service
Unit shuts down
representative
As above
Unit shuts down
EXV motor fault
Circuit A shuts down
EXV motor fault
Circuit B shuts down
Eco EXV motor fault
Circuit A shuts down
Eco EXV motor fault
Circuit B shuts down
Refrigerant leak or leak
None (alert)
detector defective
Replacement Mode:
Replacement Mode:
Please contact your
Please contact your local
local service
service representative to
representative to obtain
obtain activation key(s) to
activation key(s) to
retrieve (or activate)
retrieve (or activate)
software options
software options
See section 8.6.2
Unit shuts down
See section 8.6.2
Unit shuts down
Reset type
Automatic (the first alarm 
within the last 24 hours);
otherwise Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Automatic
Automatic, if Software
Activation Key is installed
Automatic, if Software
Activation Key is not
provided within 7 days
since the first compressor 
start (the alarm will be reset
and software-protected
options will be blocked)
Manual
Manual