32
A B B U P S P R O D U C T S A N D S O L U T I O N S
02: ECO setting (only available or effective on bypass mode, standby mode, Line mode and ECO mode)
Interface
S y s t e m : E c o
S t a t u s : D i s a b l e
H i g h L o s s V : 1 2 6 V
L o w L o s s V : 1 1 4 V
H i g h L o s s F : 5 2 H z
L o w L o s s F : 4 8 H z
> > >
03: Output setting (only available or effective on bypass mode and standby mode)
Interface
O u t p u t :
V o l t :
F r e q :
Y Y i i _ _ L L i i u u
2 2 0 0 2 2 2 2 - - 0 0 1 1 - - 2 2 1 1
C V C F : D i s a b l e
04: SystemTime setting (available or effective on all mode)
Interface
S y s t e m : T i m e T e m p
S y s t e m T i m e :
Y Y i i _ _ L L i i u u
2 2 0 0 2 2 2 2 - - 0 0 1 1 - - 2 2 1 1
T e m p e r a t u r e
> > >
Description
1.Status
Enable: ECO function enabled
Disable: ECO function disabled
If ECO function is disabled, voltage range and frequency range for ECO mode still can be
set, but it is meaningless unless the ECO function is enabled. The default setting is
Disable.
2.HighLoss V: High voltage point in ECO mode. The setting range is from (Rated Output
Volt +11V) to (Rated Output Volt +24V) and the default setting is (Rated Output Volt
+11V).
3.LowLoss V: Low voltage point in ECO mode. The setting range is from (Rated Output
Volt -24V) to (Rated Output Volt-11V) and the default setting is (Rated Output Volt -11V).
4.HighLoss F: Set High frequency point for ECO mode.
50 Hz system: Setting range is from 52Hz to 54Hz.
60 Hz system: Setting range is from 62Hz to 64Hz.
The default value is 52Hz/62Hz.
5.LowLoss F: Set Low frequency point for ECO mode.
50 Hz system: Setting range is from 46Hz to 48Hz.
60 Hz system: Setting range is from 56Hz to 58Hz.
The default value is 48Hz/58Hz.
Description
1.Volt:
100: Presenting the rated output voltage with 100Vac
110: Presenting the rated output voltage with 110Vac
115: Presenting the rated output voltage with 115Vac
120: Presenting the rated output voltage with 120Vac
127: Presenting the rated output voltage with 127Vac
The default value is 120Vac.
2.Freq:
50Hz: The output frequency is setting for 50Hz.
1 2 0 V
60Hz: The output frequency is setting for 60Hz.
A u t o
NOTE: CVCF should be enabled first to modify this item.
If CVCF is disabled, output frequency will be decided according to the latest normal
utility frequency. If it is within 46Hz and 54Hz, the output frequency will be 50.0Hz. If it is
within 56Hz to 64Hz, the output frequency will be 60.0Hz.
3.CVCF:
Enable or disable CVCF (converter) mode.
Enable: The output frequency will be fixed at 50Hz or 60Hz according to setting of
"Freq". The input frequency could be from 46Hz to 64Hz.
Disable: The output frequency will synchronize with the input frequency within 46~54 Hz
for 50Hz system or within 56~64 Hz for 60Hz system.
NOTE: CVCF means Constant Voltage and Constant Frequency. It represents converter
mode.
The default setting is Disable.
Description
2 0 2 0 - 1 2 - 1 5
Date, time and calendar date can be modified via this interface. Input the actual time, the
1 1 : 1 0 : 2 6
unit will automatically adjust timer after "ENTER" button is pressed.
T u s e d a y
3 0 C