U P S T E C H N I C A L S P E C I F I C AT I O N
INPUT CHARACTERISTICS
Acceptance voltage
(steady-state, r.m.s)
Nominal voltage
Tolerance, referred to
120/208VAC
Frequency, rated
Frequency tolerance
Input phase (L1 to L2)
Current (r.m.s), rated (with battery
charged and input 120/208V)
Current (r.m.s), maximum (with
charging batt. and input 120/208V)
Total harmonic distortion (THDi)
Power factor
Rated short-time
withstand current (I
)
CW
AC power distribution system
Phases required
Neutral required
ADDITIONAL AND USUAL INFORMATION
Connection
Cable entry
Walk In/Soft Start
5 kVA
88-155VAC (L-N)/
152-269VAC (L-L)
120/208, 120/240,
100/200, 110/220,
115/230, 127/220 VAC
115/230, 127/220 VAC
-20% / +25%
50 Hz / 60 Hz (selectable)
50 Hz / 60 Hz (selectable)
46 Hz – 54 Hz
(50 Hz system) /
56 Hz – 64 Hz
(60 Hz system)
20.8
21.8A
< 4 % @ 100% R Load
≥0.99 @ 100% load
6kA for 1.5 cycles
TN-S, TT
2
Yes
Rear
(Power supply needed only for first start-up)
6 kVA
88-155VAC (L-N)/
88-155VAC (L-N)/
152-269VAC (L-L)
120/208, 120/240,
120/208, 120/240,
100/200, 110/220,
100/200, 110/220,
115/230, 127/220 VAC
-20% / +25%
50 Hz / 60 Hz (selectable)
46 Hz – 54 Hz
(50 Hz system) /
56 Hz – 64 Hz
(60 Hz system)
120°±10%, 180°±10%, 240°±10%
25
26A
< 4 % @ 100% R Load
< 4 % @ 100% R Load
≥0.99 @ 100% load
≥0.99 @ 100% load
6 kA for 1.5 cycles
6 kA for 1.5 cycles
2
Yes
4 w i res, 2 phase + N + PE
Rear
Yes
8 kVA
88-155VAC (L-N)/
152-269VAC (L-L)
152-269VAC (L-L)
120/208, 120/240,
100/200, 110/220,
115/230, 127/220 VAC
-20% / +25%
50 Hz / 60 Hz (selectable)
46 Hz – 54 Hz
(50 Hz system) /
(50 Hz system) /
56 Hz – 64 Hz
(60 Hz system)
(60 Hz system)
33.3
34.3A
< 4 % @ 100% R Load
≥0.99 @ 100% load
6 kA for 1.5 cycles
2
Yes
Rear
47
10 kVA
-20% / +25%
46 Hz – 54 Hz
56 Hz – 64 Hz
41.7
42.7A
2
Yes
Rear