2 M A I N T E N A N C E

2 Maintenance

DANGER
DANGER
PowerValue RT G2 5-10 kVA UL requires only
minimal maintenance.
Charge the UPS regularly to maximize the
expected life of the battery. When connected to
mains power, the UPS charges the batteries and
prevents the batteries from overcharging and
over-discharging.
• Replace the batteries when the battery service
life has been exceeded (around three to five
years at 25 °C ambient temperature). Contact
your local ABB or an agent authorized by ABB for
replacements.
• Charge the UPS once every four to six months if
it is not used regularly.
• In high-temperature regions, charge and
discharge the battery every two months. The
standard charging time should be at least 12
hours.
• Replace the battery when the discharge time is
less than 50 percent of specified after fully
charging. Check the battery connection or
contact your local dealer to order a new battery.
DANGER
WARNING
WARNING
TO PREVENT RISK OF ELECTRIC SHOCK,
ONLY QUALIFIED PERSONNEL MAY
REMOVE THE UPS COVER
TO PREVENT RISK OF SHOCKS AND RISK
OF FAILURE DO NOT CUT, REWORK OR
MANIPULATE THE MATERIAL DELIVERED
WITH THE UPS
SERVICING OF BATTERIES INVOLVES
ENERGY AND SHOCK HAZARD AND
SHOULD BE PERFORMED BY PERSONNEL
KNOWLEDGEABLE ABOUT BATTERIES
AND REQUIRED PRECAUTIONS
DO NOT DISPOSE OF BATTERIES IN A FIRE.
THE BATTERIES MAY EXPLODE
DO NOT OPEN OR MUTILATE BATTERIES.
RELEASED ELECTROLYTE IS HARMFUL TO
THE SKIN AND EYES. IT MAY BE TOXIC
COMPONENTS INSIDE THE UPS ARE
CONNECTED TO THE BATTERY EVEN
WHEN THE UPS IS DISCONNECTED FROM
THE MAINS POWER SUPPLY.
DANGER
DISCONNECT THE BATTERIES BEFORE
CARRYING OUT ANY KIND OF SERVICE
AND/OR MAINTENANCE. VERIFY THAT NO
CURRENT IS PRESENT, AND NO
HAZARDOUS VOLTAGE EXISTS IN THE
DANGER
CAPACITOR OR BUS CAPACITOR
TERMINALS.
THE BATTERY CIRCUIT IS NOT ISOLATED
FROM THE INPUT VOLTAGE. HAZARDOUS
VOLTAGES MAY OCCUR BETWEEN THE
BATTERY TERMINALS AND THE GROUND.
VERIFY THAT NO VOLTAGE IS PRESENT
DANGER
BEFORE SERVICING.
A BATTERY CAN PRESENT A RISK OF
ELECTRICAL SHOCK AND HIGH SHORT-
CIRCUIT CURRENT. THE FOLLOWING
PRECAUTIONS SHOULD BE OBSERVED
WHEN WORKING ON BATTERIES:
• REMOVE WATCHES, RINGS OR OTHER
METAL OBJECTS
• MAKE USE OF PROPER PPE (PERSONAL
PROTECTION EQUIPMENT) AS PER
LOCAL POLICIES AND RULES
- WEAR FLAME/ARC RESISTANT
WHOLE BODY CLOTHING
- WEAR SUITABLE VOLTAGE RATED
DANGER
GLOVES
- USE SAFETY DIELECTRIC FOOTWEAR
- WEAR ARC FLASH FACE SHIELD
- USE VOLTAGE RATED TOOLS
• DO NOT LAY TOOLS OR METAL PARTS
ON TOP OF BATTERIES
• DISCONNECT THE CHARGING SOURCE
PRIOR TO CONNECTING OR
DISCONNECTING BATTERY TERMINALS.
WHEN REPLACING BATTERIES, REPLACE
WITH THE SAME TYPE AND NUMBER OF
BATTERIES OR BATTERY PACKS
WARNING
REPLACE FUSES ONLY WITH FUSES OF
THE SAME TYPE AND OF THE SAME
AMPERAGE TO AVOID FIRE HAZARDS.
WARNING