5 O P E R AT I O N
5.5.2-4. Setting
This page is used to configure the parameter settings. There are submenus under the Setting, including
Bypass, ECO, Output, SystemTime, Others and Battery, as shown below.
C o n t r o l
M e a s u r e m e n t
S e t t i n g
I n f o r m a t i o n
E v e n t s
NOTE
01: Bypass setting (only available or effective on bypass mode and standby mode)
Interface
Y Y i i _ _ L L i i u u
Y Y i i _ _ L L i i u u
2 2 0 0 2 2 2 2 - - 0 0 1 1 - - 2 2 1 1
B y p a s s :
S t a t u s : O p e n
H i g h L o s s V : 1 2 6 V
L o w L o s s V : 1 1 4 V
H i g h L o s s F : 5 2 H z
L o w L o s s F : 4 8 H z
Y Y i i _ _ L L i i u u
Main
Menu
Enter Setting:
Yes
No
SOME SETTINGS WILL BE ONLY AVAILABLE IN SOME OPERATION MODES. IF THE SETTING IS NOT
AVAILABLE IN CURRENT MODE, THE LCD WILL SHOW PROMPT MESSAGE WITH "ITEM CAN'T BE SET IN THIS
MODE". PRESS ANY BUTTON OR JUST WAIT FOR SEVERAL SECONDS UNTIL THIS MESSAGE FADES.
Description
1. Status
1.1 Open/Forbid:
Open: Bypass allowed. When selected, UPS will run at Bypass mode depending on bypass
enabled/disabled setting.
Forbid: Bypass not allowed. When selected, it's not allowed for running in Bypass mode
under any situations.
The default setting is Open .
1.2 Enable/Disable
Y Y i i _ _ L L i i u u
2 2 0 0 2 2 2 2 - - 0 0 2 2 - - 1 1 7 7
2 2 0 0 2 2 2 2 - - 0 0 4 4 - - 1 1 4 4
This option appears only when Bypass status is set to "Open".
Enable: Bypass enabled. When selected, Bypass mode is activated.
Disable: Bypass disabled. When selected, automatic bypass is acceptable, but "manual
bypass" is not available. "Manual bypass" means users manually operate UPS to Bypass
D i s a b l e
mode (for example, in AC mode turning off the UPS to Bypass mode). Then, the UPS will
go to bypass mode but without output if it is turned off in AC mode.
The default setting is Enable.
NOTE: The following items are only available in bypass mode.
2. HighLoss V: Set the acceptable high voltage for bypass. Setting range is from (rated
Output volt+6V) to 155V and the default value is 140V.
3. LowLoss V: Set the acceptable low voltage for bypass. Setting range is from 88V to
(rated Output volt-6V) and the default value is 88V.
4. HighLoss F: Set the acceptable high frequency for bypass.
50 Hz system: Setting range is from 51Hz to 54 Hz.
60 Hz system: Setting range is from 61Hz to 64Hz.
The default value is 54.0Hz/64.0Hz.
5. LowLoss F: Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46Hz/56Hz.
2 2 0 0 2 2 2 2 - - 0 0 4 4 - - 1 1 4 4
Select"Yes"
Setting
Yes or No?
Select"No"
S e t t i n g :
B y p a s s
E c o
O u t p u t
S y s t e m
O t h e r s
B a t
D r y C o n t a c t
31
Bypass
Eco
Output
System Time
Others
Bat
DryContact