9.6

Final settings and checks

Final settings
1. Activate the application-specific relay module functionalities. (Optional, only for control
devices with a relay module)
Proceed as described in the section Relay module (Page 72).
2. Configure the connected sensor type.
3. Switch on the control device by connecting the power supply to the control device and to the
network.
The four LEDs alongside the plug connector X6 indicate which control signal is currently
active. If input 1 is configured as a light barrier input and there is no obstacle in the travel
direction, the LED for light barrier/DCPS input lights up continuously.
If the control signal CLOSE is present, the door moves into the CLOSED position at initial
speed.
If an OPEN control signal is set, the door moves into the OPEN position at initial speed. The
OPEN signal has priority over the CLOSE signal!
Once the controller has detected the door OPEN and CLOSED end positions, the subsequent
opening and closing movements proceed at normal speed once again.
Note
An opening or closing command must be present until the entire travel distance from OPEN to
CLOSE or from CLOSE to OPEN can be completely traversed and the doors dwells for an additional
second in the OPEN and CLOSE door position.
Final checks
Final check of the permissible energies and forces.
Risk of injury due to moving mechanical parts
Check permissible forces and energies after the door drive has been commissioned in the
complete system and adjust them if they exceed their limit values.
Please observe the valid applicable standards and directives for the respective application, as
well as the following guidelines:
• Gearing up or down is not allowed on the toothed belt because this would change the
AT40 and ATD400V for elevators
System Manual, 06/2022, A5E42192709-AH
WARNING
kinetic energies or static forces on the door. The door width would then no longer be valid.
Connecting and commissioning
9.6 Final settings and checks