5.7 Operating and parameterizing controllers
If the DOOR OPEN and DOOR CLOSE commands are issued simultaneously, the door always
moves in the OPEN direction.
Note
Operating SIDOOR SERVICE TOOL, SIDOOR SUPPORT App or SIDOOR USER SOFTWARE
Alternatively, you can also control the doors via the SIDOOR SERVICE TOOL, the SIDOOR
SUPPORT app or the SIDOOR USER SOFTWARE. In this case, the external input signals are
blocked. Additional information is available in the section SIDOOR SERVICE TOOL (Page 141) and
in the SIDOOR SOFTWARE KIT Operating Instructions
ww/en/view/92711247).
5.7.1.2

Minimal editor

Using the minimal editor
The SIDOOR AT40 and ATD400V control devices have a minimal editor.
The minimal editor is a utility for changing specific parameters on a control unit when the
terminal module, the SIDOOR SERVICE TOOL, SIDOOR SUPPORT app or the SIDOOR USER
SOFTWARE is not available. In this case, the learn run button (S401) and the two service buttons
(S402, S403) are assigned second functions. The 7-segment display (H401) is used to visualize
messages.
You can use the minimal editor to perform the following settings:
• Select a fixed profile
• Set the closing forces (input of the counterweight)
• Setting the light barrier functionality
Risk of injury due to moving mechanical parts
Selecting a profile overwrites the specification of the counterweight.
For this reason, set the value for the counterweight (parameter "A") last.
The minimal editor can only be activated by pressing the service buttons S402 and S403 at the
same time as the network is reset.
Activating the minimal editor
1. Disconnect the control device from the power supply by pulling the power plug.
The line voltage can alternatively be connected and disconnected with the X3 connector
directly on the control device.
2. Press and hold down the S402 and S403 buttons simultaneously and reestablish the line
voltage by plugging the power plug back in. Continue to hold down both buttons.
3. An "8" appears on the 7-segment display for approximately 5 seconds as confirmation.
88
WARNING
(https://support.industry.siemens.com/cs/
AT40 and ATD400V for elevators
System Manual, 06/2022, A5E42192709-AH