VAT 653 Series Installation, Operating, & Maintenance Instructions page 71

Pendulum control & isolation valve with devicenet® interface
Table of Contents

Advertisement

Series 65
Command
GAIN
SENSOR MODE
ZERO CONTROL
ZERO ADJUST
Note: Pressure Reading and Offset Values of Sensor 1 and Sensor 2 are in Pressure Controller Object (Class ID 100)
982156EB
INSTALLATION
Service Code
Class ID
Set
16
49
Get
14
X:
Gain, max. value is 3.2767, data type is floating point
This command selects the gain for PRESSURE/POSITION and allows for scaling.
Default value is 1.0
Example:
Gain
X (hex)
0.1
3D CC CC CC
1.0
3F 80 00 00
3.2767
40 51 B5 73
Set
16
49
Get
14
X:
0 = no sensor
1 = sensor 1
2 = sensor 1 high, sensor 2 low, crossover fade
7 = sensor 1 high, sensor 2 low, crossover target pressure
9 = sensor 1 high, sensor 2 low, crossover switch point
3 = sensor 2
4 = sensor 2 high, sensor 1 low, crossover fade
8 = sensor 2 high, sensor 1 low, crossover target pressure
10 = sensor 2 high, sensor 1 low, crossover switch point
2 sensor operation are possible with 2 sensor hardware [950..-...Q -....] only.
For applications where the high range sensor is used for monitoring purpose
only, select sensor operation modes 1 or 3 for pressure control with low range
sensor and read high range sensor from SENSOR 1 READING resp. SENSOR
2 READING.
Set
16
49
Get
14
X:
0
Disable
1
Enable
In case ZERO CONTROL is disabled ZERO ADJUST does not work.
75
49
This service initiates ZERO ADJUST.
Note: Refer to «Zero adjust» for correct zero procedure.
Edition 2019-06-05
Instance ID
Attribute ID
Description
1 Pressure
14
3 Position
Resulting range
0 ... 1000
0 ... 10000
0 ... 32767
1
101
1
102
1
-
Service
Service
data length
data field
(number of bytes)
4 float
X
1
X
1
X
0
-
71/110