4.7.4.1
Pressure ramp configuration
Time Mode (Ramp Mode = Time)
The time within Target Pressure Used (ramp) reaches a
new Target Pressure is defined in parameter value
Ramp Time. Ramp Time is a value in the unit [seconds].
21
19
17
15
13
11
9
7
5
0
50/110
INSTALLATION
5
10
time
Target Pressure
Target Pressure Used (ramp)
Edition 2019-06-05
Slope Mode (Ramp Mode = Slope)
After setting a new Target Pressure, Target Pressure
Used will converge the Target Pressure in the slope
defines in parameter Ramp Slope. Ramp Slope is a
value in the unit [pressure / seconds]
21
19
17
15
13
11
9
7
5
0
15
Series 65
5
10
time
Target Pressure
Target Pressure Used (ramp)