Adjustment procedure:
1. Use optimal gain factor, sensor delay time and setpoint ramp according to preceding tuning steps.
2. Open valve.
3. Control a typical pressure / flow situation.
4. Repeat from step 2 with slower valve speed until required response is achieved.
Required information for support:
•
Go to 'Tools / Create Diagnostic File' in 'Control Performance Analyzer' and save file
•
Pressure / flow / gas conditions to be controlled
•
Chamber volume
•
Pumping speed (l/s) and pump type (e.g. turbo pump)
•
System description
•
Problem description
Send diagnostic file with and all required information to tuning-support@vat.ch