Honeywell FIre-LITe ALArms MS-9600LS Manual page 16

Addressable fire alarm control panel
Hide thumbs Also See for FIre-LITe ALArms MS-9600LS:
Table of Contents

Advertisement

Product Description
Maximum signaling current per circuit: 3.00 amps (see Figure 1.1 on page 17)
End-of-Line Resistor: 4.7 k, ½ watt (P/N 71252 UL listed) for NACs
Refer to Device Compatibility Document for listed compatible devices
Two Programmable and One Fixed Output Relay - TB1 & TB5
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.5 on page 47 for information on power-limited wiring for relay circuits
Four-Wire Resettable Special Application Smoke Detector Power (24 VDC nominal) -
TB3, Terminals 1 (+) & 2 (-)
Maximum ripple voltage: 10 mV
Up to 1.5 amps is available for powering 4-wire smoke detectors (see Figure 1.1)
Power-limited circuit, nonsupervised
Refer to Device Compatibility Document for listed compatible devices
Nonresettable Special Application Power #1 (24 VDC Nominal) -
TB3, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10mV
Total DC current available from each output is up to 1.5 amps (see Figure 1.1)
Power-limited circuit, nonsupervised
Nonresettable Special Application Power #2 (24 VDC Nominal) -
TB3, Terminals 5 (+) & 6 (-)
Maximum ripple voltage: 10mV
Total DC current available from each output is up to 1.5 amps (see Figure 1.1)
Power-limited circuit, nonsupervised
EIA-485 (ACS/ANN-BUS) - TB6
ACS/ANN annunciator connector, Terminal 1 (+) and Terminal 2 (-)
EIA-485 (TERM) - TB7
Terminal Mode annunciator connector, Terminal 5 (In +), 6 (In -), 7 (Out +), 8 (Out -)
Supervised, power-limited.
EIA-232 Serial - TB7
Local serial PC/Printer Connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground)
Non-supervised, power-limited.
16
RMS
RMS
RMS
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010