11: Phone Line; 12: Central Station - Honeywell FIre-LITe ALArms MS-9600LS Manual

Addressable fire alarm control panel
Hide thumbs Also See for FIre-LITe ALArms MS-9600LS:
Table of Contents

Advertisement

Read Status
4.22.11 Phone Line
4.22.12 Central Station
READ STATUS
1=ANNUNCIATORS
2=PHONE LINE
3=CENTRAL STATION
Read Status Screen #4
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Pressing 2 while viewing Read Status Screen #4 will display the following screen:
PRIMARY
SECONDARY TOUCHTONE
3=SUPERV PHONE LINE
The second and third lines of this screen indicate that both the Primary and Secondary phone lines
have been configured for touchtone dialing operation.
Pressing 3 while viewing the Phone Line screen will cause the following screen to be displayed:
SUPERVISE PHONE LINE
PHONE LINE 2
This screen indicates whether or not Phone Line 2 is being supervised. In this example, PHONE
LINE 2 NO indicates the phone line is not being supervised.
Pressing 3 while viewing Read Status Screen #4 will display the following screens:
REPORTING
REPORT
CALL LIMIT
1=PRIMARY
2=SECONDARY
REPORT STYLE
Central Station Screen #1 indicates whether the Central Station Reporting is enabled or disabled, if
the Reports will be sent to the First Available or Backup Primary and Secondary Central Station
phone numbers and Call Limit for DACT trouble calls within a 24 hour period. Central Station
Screen #2 provides information on the Report Style (Zone or Point) as well as the Primary and Sec-
ondary Central Station programming which includes:
Test Time Interval
Account Code
24 Hour Test Time
Phone Number
Communication Format
Event Codes
PHONE LINE
TOUCHTONE
CENTRAL STATION
ENABLED
FIRST AVAIL
Central Station Screen #1
CENTRAL STATION
Central Station Screen #2
Operating Instructions
NO
10
ZONE
169