Installation
2.6.1 DACT-UD2 Installation
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
!
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
The DACT-UD2 Digital Alarm Communicator/Transmitter, which is supplied standard with the
MS-9600UDLS/E, transmits system status to UL listed Central Station receivers via the public
switched telephone network. It is capable of reporting up to 99 software zones or up to 636
addressable points. Two modular phone jacks, labeled PRI for Primary phone line and SEC for
Secondary phone line, allow easy connection of two independent telephone lines to the DACT-
UD2. The following functions have been incorporated into the DACT-UD2:
Line Seizure - takes control of phone lines disconnecting any premises phones
Off/On Hook - performs on and off-hook status to the phone lines
Listen for dial tone - 440 hertz tone typical in most networks
Dialing Central Station(s) number - default is Touch-Tone®, programmable to rotary
For tone burst or touchtone type formats: determine proper 'Acknowledge' and 'Kissoff'
tone(s) - the frequency and time duration of the tone(s) varies with the transmission format.
The control panel will adjust accordingly
Communicate in the following formats:
• Ademco Contact ID
• SIA
The DACT-UD2 module plugs into connector J2 on the FACP main circuit board.
J5 Connector (located on
back of module) plugs into J2
on FACP main circuit board
52
SEC
Secondary Phone Line
Figure 2.11 DACT-UD2 Module
Optional Modules and Devices
PRI
Primary Phone Line
J4
USB Port
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010