NFPA Standard-Specific Requirements
C.2 MBT-1 Municipal Box Trip - Silenceable
The following figure illustrates the connection of the MBT-1 (Municipal Box Trip) between the
FACP and a Local Energy Municipal Box. The use of an addressable control module programmed
for General Alarm and Silenceable allows silencing of the Municipal Box without resetting the
panel or box.
programmed as Silenceable
Alarm polarity shown!
-
+
+
-
24 VDC, Nonresettable
194
The CMF-300 must be
and General Alarm.
CMF-300
FACP
MBT-1 Municipal Box Trip - Silenceable
Connect wires to two
red terminals on box.
Note: 10 maximum loop
resistance due to wiring from
power supply to Municipal Box.
(All contacts shown in energized position)
- To next device
+ on SLC Loop
Braided-shield/Drain Wire
EOLR-1 Power
Supervision Relay
SLC Loop
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Gamewell Model
M34-56 Local Energy
Municipal Box
white wire
MBT-1
brown wire
red
B+
-B
Shield
black