Annunciator addressing is specific to the FACP control panel. The following table describes the
annunciator addresses and the corresponding addressable devices that will be annunciated at each
annunciator address.
ACS Annunciator Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
The 8 General System Status Points include the following:
•
General Alarm
•
General Trouble
•
General Supervisory
•
Alarm Silenced
•
System Off Normal
•
AC Loss
•
Battery Fault
•
NAC Fault
Pressing 3 while viewing the ACS Options screen will toggle the display between UDACT NO and
UDACT YES. This allows the connection of an external UDACT (Universal Digital Alarm Com-
municator/Transmitter).
120
Annunciator Displays the Following Points
8 General System Status Points & Zones 1 - 56
Zones 57 - 99 & 4 NACs
Loop 1, Module Addresses 1 - 64
Loop 2, Module Addresses 1 - 64
Loop 1, Module Addresses 65 - 128
Loop 2, Module Addresses 65 - 128
Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159
Loop 1, Detector Addresses 1 - 64
Loop 2, Detector Addresses 1 - 64
Loop 1, Detector Addresses 65 - 128
Loop 2, Detector Addresses 65 - 128
Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159
not used
not used
not used
not used
not used
not used
not used
8 General System Status Points & Zones 1 - 56
Zones 57 - 99 & 4 NACs
Loop 1, Module Addresses 1 - 64
Loop 2, Module Addresses 1 - 64
Loop 1, Module Addresses 65 - 128
Loop 2, Module Addresses 65 - 128
Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159
Loop 1, Detector Addresses 1 - 64
Loop 2, Detector Addresses 1 - 64
Loop 1, Detector Addresses 65 - 128
Loop 2, Detector Addresses 65 - 128
Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159
not used
Master Programming Level
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010