The load encroachment element responds to the positive-sequence voltage and current and applies a characteristic shown
in the figure below.

LOAD ENCROACHMENT

The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be
used to block selected protection elements such as distance or phase overcurrent. The following figure shows an effect of
the load encroachment characteristics used to block the quadrilateral distance element.
GE Multilin
SETTING GROUP 1(6)
LOAD ENCROACHMENT
FUNCTION: Disabled
LOAD ENCROACHMENT
SOURCE: SRC 1
LOAD ENCROACHMENT
MIN VOLT: 0.250 pu
LOAD ENCROACHMENT
REACH: 1.00 Ω
LOAD ENCROACHMENT
ANGLE: 30°
LOAD ENCROACHMENT
PKP DELAY: 0.000 s
LOAD ENCROACHMENT
RST DELAY: 0.000 s
LOAD ENCRMNT BLK:
Off
LOAD ENCROACHMENT
TARGET: Self-reset
LOAD ENCROACHMENT
EVENTS: Disabled
X
–REACH
OPERATE
Figure 5–73: LOAD ENCROACHMENT CHARACTERISTIC
D30 Line Distance Protection System
5.6 GROUPED ELEMENTS
5.6.6 LOAD ENCROACHMENT

LOAD ENCROACHMENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.02 to 250.00 ohms in steps of 0.01
Range: 5 to 50° in steps of 1
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Flexlogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
REACH
R
LOAD ENCROACHMENT
OPERATE
827846A1.CDR