Transmission Error Between Centralized Controller And Indoor Unit - Daikin VRV S RXQ4/5ARV1 Service Manual

Table of Contents

Advertisement

SiAF332111E
5.66 Transmission Error between Centralized Controller and
Indoor Unit
Applicable
All indoor unit models
Schedule timer
Models
Central remote controller
intelligent Touch Controller
UE
Error Code
Method of Error
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Detection
Error Decision
Transmission is not carried out normally for a certain amount of time
Conditions
Supposed
 Transmission error between optional controllers for centralized controller and indoor unit
Causes
 Connector for setting main controller is disconnected.
 Defective PCB for central remote controller
 Defective indoor unit PCB
Part 6 Service Diagnosis
(or disconnection of connector for independent / combined use changeover switch.)
Troubleshooting by Error Code
321