Troubleshooting
7.6.2 Inverter Compressor Motor Lock
E5
Error Code
LRMEQ3~4BY1
Applicable
Models
Inverter PCB takes the position signal from UVW line connected between the inverter and
Method of Error
compressor, and the error is detected when any abnormality is observed in the phase-current
Detection
waveform.
This error will be output when the INV. compressor motor does not start up even in forced
Error Decision
startup mode.
Conditions
INV. compressor lock
Supposed
High differential pressure (0.5MPa or more)
Causes
Incorrect UVW wiring
Defective or wrong inverter PCB
Stop valve is not opened
Slugging state of refrigerant
Abrasion of sliding parts caused by wet operation due to defective secondary equipment
Failure of oil return due to defective onsite piping work
Liquid return caused by operation signal connection failure (P1/P2)