Daikin VRV S RXQ4/5ARV1 Service Manual page 58

Table of Contents

Advertisement

Service Settings Menu, Maintenance Menu
6.1.2 Maintenance Menu
Maintenance
Menu
Model Name Unit No.
Operation
Hours
Indoor Unit
Status
Outdoor Unit
Status
Error Display Display error ON
Swap Unit
No.
52
Item 2
Indoor unit
Outdoor unit
R-32 mark display
Unit No.
Indoor unit operation hours
Indoor fan operation hours
Indoor unit energized hours
Outdoor unit operation hours
Outdoor fan 1 operation hours
Outdoor fan 2 operation hours
Outdoor compressor 1
operation hours
Outdoor compressor 2
operation hours
Unit No.
FAN
Speed
FLAP
EV
MP
EH
Hu
TBF
FLOAT
T1/T2
Th1
Th2
Th3
Th4
Th5
Th6
Unit No.
FAN step
COMP
EV1
SV1
Pe
Pc
Th1
Th2
Th3
Th4
Th5
Th6
Display error OFF
Display warning ON
Display warning OFF
Current Unit No.
Transfer Unit No.
Remarks
Select the unit number you want to check.
The model names are displayed.
(A model code may be displayed instead, depending on
the particular model.)
Select the unit number you want to check.
All of these are displayed in hours.
Select the unit number you want to check.
Fan tap
Fan speed (rpm)
Airflow direction
Degree that electronic expansion valve is open (pulse)
Drain pump ON/OFF
Electric heater ON/OFF
Humidifier ON/OFF
Anti-freezing control ON/OFF
FLOAT SWITCH ON/OFF
T1/T2 input from outside ON/OFF
Suction air thermistor 1
Indoor liquid pipe thermistor
Indoor gas pipe thermistor
Discharge air thermistor 2
Infrared floor sensor 3
Control temperature 4
Select the Unit No. you want to check.
Fan tap
Compressor power supply frequency (Hz)
Degree that electronic expansion valve is open (pulse)
Solenoid valve ON/OFF
Low pressure (MPa)
High pressure (MPa)
Displays the error on the screen.
Displays neither errors nor warnings.
Displays a warning on the screen if an error occurs.
No warning is displayed.
A unit No. can be transferred to another.
SiAF332111E
Part 3 Remote Controller

Advertisement

Table of Contents
loading

Table of Contents