5.26 Activation of Low Pressure Sensor

Applicable
All outdoor unit models
Models
E4
Error Code
Method of Error
Make judgment of pressure detected by the low pressure sensor with the outdoor unit main
Detection
PCB.
Error Decision
When low pressure caused a drop while the compressor is in operation:
Conditions
 Operating pressure: 0.07 MPa
Supposed
 Abnormally drop in low pressure
Causes
 Defective low pressure sensor
 Defective outdoor unit main PCB
 The stop valve is not opened
Part 6 Service Diagnosis
Troubleshooting by Error Code
235