Daikin VRV S RXQ4/5ARV1 Service Manual page 246

Table of Contents

Advertisement

Troubleshooting by Error Code
After replacing the compressor, perform troubleshooting on the compressor based on CHECK 3
and CHECK 5.
Reference
CHECK 3 Refer to page 339.
Reference
CHECK 4 Refer to page 340.
Reference
CHECK 5 Refer to page 344.
Reference
CHECK 12 Refer to page 353.
240
A
Are
the high/low
pressure measured
by the service checker the
same as the actual measured
voltage values of the
high/low pressure
sensors?
YES
CHECK 4
NO
Is the power transistor
normal?
YES
NO
SiAF332111E
Replace the outdoor
unit main PCB
(A1P).
Replace the inverter PCB
(A3P).
Replace the compressor.
Part 6 Service Diagnosis