Control for 6/8 HP Outdoor Unit
2.5.5 Electronic Expansion Valve Control
Electronic expansion valve Y1E
Cooling: electronic expansion valve is used only at fully closed or fully open condition:
2.5.6 Step Control of Outdoor Fans
Used to control the revolutions of outdoor fans in the steps listed in table below, according to
condition changes.
* When the system detects that outdoor air temperature (Ta) reaches 41°C or more, the control
of fan revolutions will be changed to 1,060 rpm automatically.
Note(s)
Table shown above is for external static pressure level 0. In case of high external static
When capacity priority mode is set, values may differ.
74
Compressor(s) OFF: fully closed (0 pulse).
Compressor ON:
Fully open (480 pulses)
Normally, the control is used to reduce the PCB temperature.
Compressor
0 Hz
Main
480
Y1E
pulses
0
Step No.
0
1
2
3
4
5
6
7Y
7X
8
pressure, the unit will re-adjust fan revolutions automatically and values may differ.
Fan revolutions (rpm)
RXMQ6AR
0
200
250
300
360
420
490
560
630
700
SiAF332111E
RXMQ8AR
0
440
440
440
440
480
550
650
830
960*
Part 4 Functions and Control