Test Operation (4/5/10/12 HP Models)
5.3

Test Operation (4/5 HP Models)

To start smoothly, a crankcase heater is equipped to the 5 HP unit only & to power up the
crankcase heater in advance, be sure to turn on the power supply 6 hours before operation.
Crankcase heater is not provided for 4 HP unit. So, there is no need to turn on the power supply
6 hours before operation.
Warning
Be sure to inform other installers or attach the front panel well before leaving with the power
supply turned on for the outdoor unit.
Before powering ON
 Protect the electronic components with insulating tape in accordance with the Service
 All indoor units connected with the outdoor unit will operate automatically after powering on.
Powering On to Test Operation
 Make sure to perform a test operation first after installation (If the unit is operated with the
 After turning on the power supply, do not touch any switches excluding button switches and
 Check the state of the outdoor units and fault wiring with this operation.
(1) Attach the front panel of the outdoor unit.
(2) Turn on the power supply of the outdoor and indoor units.
Caution
Only for 5 HP, to power up the crankcase heater in advance, be sure to turn on the power
supply 6 hours before operation.
(3) Remove the front panel of the outdoor unit.
(4) Check LED display of the outdoor unit's PCB (A1P, A2P), to observe whether data
transmission is normal.
(Factory
LED display: h Light OFF k Light ON l Blinking
Caution
Don't touch the switches other than BS buttons and changeover switches of the PCB (A2P)
during setting. Doing so may result in electric shock.
(5) If customer wishes to perform LOW NOISE operation or DEMAND operation, perform setting
with the BS buttons (BS1~5) on outdoor unit's PCB (A2P).
(6) Operate the BS buttons from the opening of the insulating cover. (See Protective range of
the Service Precautions label for details)
162
Precautions label attached to the front panel.
To ensure safety, check the indoor unit installation has been completed.
indoor unit's remote controller without performing a test operation, the error code U3 will be
displayed on the remote controller and the unit will not operate normally).
changeover switches when setting the outdoor unit PCB (A2P).
(For positions of the BS buttons (BS1~5) and changeover switches (DS1-1, 2) on the PCB,
refer to the Service Precautions label)
A1P
SERVICE
LED
MONITORING
MODE
LAMP
display
HAP
setting)
l
C/H CHANGEOVER
READY /
ABNORMAL
IND
H1P
H2P
H3P
h
h
k
SiAF332111E
A2P
LOW
NOISE
MASTER
SUB
H4P
H5P
H6P
h
h
h
Part 5 Field Settings and Test Operation
DEMAND
H7P
h