Field Settings for Indoor Unit
1.4.18 Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material
kit of air discharge outlet has been installed.) The second code No. is factory set to 01.
13 (23)
1.4.19 Swing Pattern Settings
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed
side by side are set to swing in an opposite direction to agitate airflow to reduce temperature
irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
13 (23)
1.4.20 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
 FXFSQ-AR, FXAQ-P
13 (23)
Note(s)
1. Some indoor unit models are not equipped with draft prevention (upward) function.
2. When the model FXFSQ-AR is attached with a closing member kit, set the Second Code No.
104
Mode
First
Second
No.
Code No.
Code No.
01
1
02
03
Mode
First
Second
No.
Code No.
Code No.
01
2
02
03
Mode
First
Second
No.
Code No.
Code No.
01
4
02
03
to 02 or 03.
Contents
4-way airflow
3-way airflow
2-way airflow
Contents
All direction synchronized swing
Facing swing
Contents
Draft prevention (upward)
Standard
Ceiling soiling prevention (downward)
Part 5 Field Settings and Test Operation
SiAF332111E
: Factory setting
: Factory setting
: Factory setting